agent_type stringlengths 4 82 | authority stringclasses 2
values | citation stringclasses 7
values | derived_fields listlengths 2 2 | id stringlengths 43 122 | interval stringlengths 1 58 | obligation stringclasses 4
values | source stringclasses 2
values | source_quote stringlengths 181 1.54k | url stringlengths 127 206 | verified_fields listlengths 2 4 | shell_material stringclasses 5
values |
|---|---|---|---|---|---|---|---|---|---|---|---|
Portable fire extinguishers | NFPA 10 (2010 ed.) | NFPA 10(10), Sec. 7.3 | [
"authority",
"obligation"
] | nfpa-10-2010-ed-annual-maintenance-portable-fire-extinguishers | at least once a year | Annual maintenance | https://www.health.state.mn.us/facilities/regulation/engineering/docs/lscfireext.pdf | “Maintenance” is a thorough examination and repair, as needed, of your facility’s portable fire extinguishers and is covered in NFPA 10(10), Sec. 7.3. Maintenance is required at least once a year – more frequently when indicated by a routine monthly inspection, as discussed earlier. | https://referencesource.org/fire-extinguisher-inspection-testing-intervals-by-type/nfpa-10-2010-ed-annual-maintenance-portable-fire-extinguishers/ | [
"agent_type",
"citation",
"interval"
] | null |
Carbon dioxide | NFPA 10 (2010 ed.) | NFPA 10(10), Sec. 8.3.1 and Table 8.3.1 | [
"authority",
"obligation"
] | nfpa-10-2010-ed-hydrostatic-test-carbon-dioxide | every 5 years | Hydrostatic test | https://www.health.state.mn.us/facilities/regulation/engineering/docs/lscfireext.pdf | Hydrostatic testing intervals for fire extinguishers are outlined in NFPA 10(10), Sec. 8.3.1 and Table 8.3.1. Test intervals for some of the most commonly found extinguishers are as follows: o Pressurized water, water mist, carbon dioxide and wet chemical (e.g. K-type) extinguishers – every 5 years | https://referencesource.org/fire-extinguisher-inspection-testing-intervals-by-type/nfpa-10-2010-ed-hydrostatic-test-carbon-dioxide/ | [
"agent_type",
"citation",
"interval"
] | null |
Dry chemical extinguishers | NFPA 10 (2010 ed.) | NFPA 10(10), Sec. 8.3.1 and Table 8.3.1 | [
"authority",
"obligation"
] | nfpa-10-2010-ed-hydrostatic-test-dry-chemical-extinguishers | every 12 years | Hydrostatic test | https://www.health.state.mn.us/facilities/regulation/engineering/docs/lscfireext.pdf | Hydrostatic testing intervals for fire extinguishers are outlined in NFPA 10(10), Sec. 8.3.1 and Table 8.3.1. Test intervals for some of the most commonly found extinguishers are as follows: o Pressurized water, water mist, carbon dioxide and wet chemical (e.g. K-type) extinguishers – every 5 years o Dry chemical extin... | https://referencesource.org/fire-extinguisher-inspection-testing-intervals-by-type/nfpa-10-2010-ed-hydrostatic-test-dry-chemical-extinguishers/ | [
"agent_type",
"citation",
"interval"
] | null |
Nonrechargeable stored pressure extinguishers | NFPA 10 (2010 ed.) | NFPA 10(10), Sec. 7.3.1.2.1.3 | [
"authority",
"obligation"
] | nfpa-10-2010-ed-hydrostatic-test-nonrechargeable-stored-pressure-extinguishers | removed from service 12 years from the date of manufacture | Hydrostatic test | https://www.health.state.mn.us/facilities/regulation/engineering/docs/lscfireext.pdf | As mentioned earlier, the exception to the rule for hydrostatic testing is nonrechargeable stored pressure extinguishers (e.g. dry chemical extinguishers), which are required to be removed from service 12 years from the date of manufacture [see NFPA 10(10), Sec. 7.3.1.2.1.3]. | https://referencesource.org/fire-extinguisher-inspection-testing-intervals-by-type/nfpa-10-2010-ed-hydrostatic-test-nonrechargeable-stored-pressure-extinguishers/ | [
"agent_type",
"citation",
"interval"
] | null |
Pressurized water | NFPA 10 (2010 ed.) | NFPA 10(10), Sec. 8.3.1 and Table 8.3.1 | [
"authority",
"obligation"
] | nfpa-10-2010-ed-hydrostatic-test-pressurized-water | every 5 years | Hydrostatic test | https://www.health.state.mn.us/facilities/regulation/engineering/docs/lscfireext.pdf | Hydrostatic testing intervals for fire extinguishers are outlined in NFPA 10(10), Sec. 8.3.1 and Table 8.3.1. Test intervals for some of the most commonly found extinguishers are as follows: o Pressurized water, water mist, carbon dioxide and wet chemical (e.g. K-type) extinguishers – every 5 years | https://referencesource.org/fire-extinguisher-inspection-testing-intervals-by-type/nfpa-10-2010-ed-hydrostatic-test-pressurized-water/ | [
"agent_type",
"citation",
"interval"
] | null |
Dry chemical extinguishers | NFPA 10 (2010 ed.) | NFPA 10(10), Sec. 8.3.1 and Table 8.3.1 | [
"authority",
"obligation"
] | nfpa-10-2010-ed-hydrostatic-test-stainless-steel-shells-dry-chemical-extinguishers | every 5 years | Hydrostatic test | https://www.health.state.mn.us/facilities/regulation/engineering/docs/lscfireext.pdf | Hydrostatic testing intervals for fire extinguishers are outlined in NFPA 10(10), Sec. 8.3.1 and Table 8.3.1. Test intervals for some of the most commonly found extinguishers are as follows: o Pressurized water, water mist, carbon dioxide and wet chemical (e.g. K-type) extinguishers – every 5 years o Dry chemical extin... | https://referencesource.org/fire-extinguisher-inspection-testing-intervals-by-type/nfpa-10-2010-ed-hydrostatic-test-stainless-steel-shells-dry-chemical-extinguishers/ | [
"agent_type",
"citation",
"interval",
"shell_material"
] | stainless steel shells |
Water mist | NFPA 10 (2010 ed.) | NFPA 10(10), Sec. 8.3.1 and Table 8.3.1 | [
"authority",
"obligation"
] | nfpa-10-2010-ed-hydrostatic-test-water-mist | every 5 years | Hydrostatic test | https://www.health.state.mn.us/facilities/regulation/engineering/docs/lscfireext.pdf | Hydrostatic testing intervals for fire extinguishers are outlined in NFPA 10(10), Sec. 8.3.1 and Table 8.3.1. Test intervals for some of the most commonly found extinguishers are as follows: o Pressurized water, water mist, carbon dioxide and wet chemical (e.g. K-type) extinguishers – every 5 years | https://referencesource.org/fire-extinguisher-inspection-testing-intervals-by-type/nfpa-10-2010-ed-hydrostatic-test-water-mist/ | [
"agent_type",
"citation",
"interval"
] | null |
Wet chemical (e.g. K-type) | NFPA 10 (2010 ed.) | NFPA 10(10), Sec. 8.3.1 and Table 8.3.1 | [
"authority",
"obligation"
] | nfpa-10-2010-ed-hydrostatic-test-wet-chemical-e-g-k-type | every 5 years | Hydrostatic test | https://www.health.state.mn.us/facilities/regulation/engineering/docs/lscfireext.pdf | Hydrostatic testing intervals for fire extinguishers are outlined in NFPA 10(10), Sec. 8.3.1 and Table 8.3.1. Test intervals for some of the most commonly found extinguishers are as follows: o Pressurized water, water mist, carbon dioxide and wet chemical (e.g. K-type) extinguishers – every 5 years | https://referencesource.org/fire-extinguisher-inspection-testing-intervals-by-type/nfpa-10-2010-ed-hydrostatic-test-wet-chemical-e-g-k-type/ | [
"agent_type",
"citation",
"interval"
] | null |
Antifreeze type extinguishers | NFPA 10 (2010 ed.) | NFPA 10(10), Sec. 7.3.1.1.2 and Table 7.3.1.1.2 | [
"authority",
"obligation"
] | nfpa-10-2010-ed-internal-examination-antifreeze-type-extinguishers | annually | Internal examination | https://www.health.state.mn.us/facilities/regulation/engineering/docs/lscfireext.pdf | It must be noted that some types of extinguishers are required to undergo an internal examination at more frequent intervals as specified in NFPA 10(10), Sec. 7.3.1.1.2 and Table 7.3.1.1.2. For example, stored-pressure loaded-stream and antifreeze type extinguishers are required to be internally inspected annually. | https://referencesource.org/fire-extinguisher-inspection-testing-intervals-by-type/nfpa-10-2010-ed-internal-examination-antifreeze-type-extinguishers/ | [
"agent_type",
"citation",
"interval"
] | null |
Carbon dioxide | NFPA 10 (2010 ed.) | NFPA 10(10), Sec. 7.3.1.1.2 and Table 7.3.1.1.2 | [
"authority",
"obligation"
] | nfpa-10-2010-ed-internal-examination-carbon-dioxide | every 5 years | Internal examination | https://www.health.state.mn.us/facilities/regulation/engineering/docs/lscfireext.pdf | It must be noted that some types of extinguishers are required to undergo an internal examination at more frequent intervals as specified in NFPA 10(10), Sec. 7.3.1.1.2 and Table 7.3.1.1.2. For example, stored-pressure loaded-stream and antifreeze type extinguishers are required to be internally inspected annually. Car... | https://referencesource.org/fire-extinguisher-inspection-testing-intervals-by-type/nfpa-10-2010-ed-internal-examination-carbon-dioxide/ | [
"agent_type",
"citation",
"interval"
] | null |
Dry chemical extinguishers | NFPA 10 (2010 ed.) | NFPA 10(10), Sec. 7.3.1.2 | [
"authority",
"obligation"
] | nfpa-10-2010-ed-internal-examination-dry-chemical-extinguishers | Every 6 years | Internal examination | https://www.health.state.mn.us/facilities/regulation/engineering/docs/lscfireext.pdf | Every 6 years, stored pressure fire extinguishers that require a 12-year hydrostatic test (e.g. dry chemical extinguishers) must be emptied and subjected to an internal examination by a trained technician in accordance with procedures detailed in the manufacturer’s service manual and NFPA 10(10), Sec. 7.3.1.2. | https://referencesource.org/fire-extinguisher-inspection-testing-intervals-by-type/nfpa-10-2010-ed-internal-examination-dry-chemical-extinguishers/ | [
"agent_type",
"citation",
"interval"
] | null |
Nonrechargeable extinguishers | NFPA 10 (2010 ed.) | NFPA 10(10), Sec. 7.3.1.2.1.3 | [
"authority",
"obligation"
] | nfpa-10-2010-ed-internal-examination-nonrechargeable-extinguishers | removed from service 12 years from the date of manufacture | Internal examination | https://www.health.state.mn.us/facilities/regulation/engineering/docs/lscfireext.pdf | The exception to this rule is nonrechargeable extinguishers, which are required to be removed from service 12 years from the date of manufacture [see NFPA 10(10), Sec. 7.3.1.2.1.3]. | https://referencesource.org/fire-extinguisher-inspection-testing-intervals-by-type/nfpa-10-2010-ed-internal-examination-nonrechargeable-extinguishers/ | [
"agent_type",
"citation",
"interval"
] | null |
Stored pressure fire extinguishers that require a 12-year hydrostatic test | NFPA 10 (2010 ed.) | NFPA 10(10), Sec. 7.3.1.2 | [
"authority",
"obligation"
] | nfpa-10-2010-ed-internal-examination-stored-pressure-fire-extinguishers-that-require-a-12-year-hydrostatic-test | Every 6 years | Internal examination | https://www.health.state.mn.us/facilities/regulation/engineering/docs/lscfireext.pdf | Every 6 years, stored pressure fire extinguishers that require a 12-year hydrostatic test (e.g. dry chemical extinguishers) must be emptied and subjected to an internal examination by a trained technician in accordance with procedures detailed in the manufacturer’s service manual and NFPA 10(10), Sec. 7.3.1.2. | https://referencesource.org/fire-extinguisher-inspection-testing-intervals-by-type/nfpa-10-2010-ed-internal-examination-stored-pressure-fire-extinguishers-that-require-a-12-year-hydrostatic-test/ | [
"agent_type",
"citation",
"interval"
] | null |
Stored-pressure loaded-stream | NFPA 10 (2010 ed.) | NFPA 10(10), Sec. 7.3.1.1.2 and Table 7.3.1.1.2 | [
"authority",
"obligation"
] | nfpa-10-2010-ed-internal-examination-stored-pressure-loaded-stream | annually | Internal examination | https://www.health.state.mn.us/facilities/regulation/engineering/docs/lscfireext.pdf | It must be noted that some types of extinguishers are required to undergo an internal examination at more frequent intervals as specified in NFPA 10(10), Sec. 7.3.1.1.2 and Table 7.3.1.1.2. For example, stored-pressure loaded-stream and antifreeze type extinguishers are required to be internally inspected annually. | https://referencesource.org/fire-extinguisher-inspection-testing-intervals-by-type/nfpa-10-2010-ed-internal-examination-stored-pressure-loaded-stream/ | [
"agent_type",
"citation",
"interval"
] | null |
Wet chemical (e.g. K-type) | NFPA 10 (2010 ed.) | NFPA 10(10), Sec. 7.3.1.1.2 and Table 7.3.1.1.2 | [
"authority",
"obligation"
] | nfpa-10-2010-ed-internal-examination-wet-chemical-e-g-k-type | every 5 years | Internal examination | https://www.health.state.mn.us/facilities/regulation/engineering/docs/lscfireext.pdf | It must be noted that some types of extinguishers are required to undergo an internal examination at more frequent intervals as specified in NFPA 10(10), Sec. 7.3.1.1.2 and Table 7.3.1.1.2. For example, stored-pressure loaded-stream and antifreeze type extinguishers are required to be internally inspected annually. Car... | https://referencesource.org/fire-extinguisher-inspection-testing-intervals-by-type/nfpa-10-2010-ed-internal-examination-wet-chemical-e-g-k-type/ | [
"agent_type",
"citation",
"interval"
] | null |
Portable fire extinguishers | NFPA 10 (2010 ed.) | NFPA 10(10), Sec. 7.2.1 | [
"authority",
"obligation"
] | nfpa-10-2010-ed-monthly-visual-inspection-portable-fire-extinguishers | at least monthly at a minimum of 30-day intervals | Monthly visual inspection | https://www.health.state.mn.us/facilities/regulation/engineering/docs/lscfireext.pdf | Portable fire extinguishers are required to be visually inspected when initially placed in service and at least monthly at a minimum of 30-day intervals thereafter [see NFPA 10(10), Sec. 7.2.1]. | https://referencesource.org/fire-extinguisher-inspection-testing-intervals-by-type/nfpa-10-2010-ed-monthly-visual-inspection-portable-fire-extinguishers/ | [
"agent_type",
"citation",
"interval"
] | null |
portable fire extinguishers | OSHA 29 CFR 1910.157 | null | [
"authority",
"obligation"
] | osha-29-cfr-1910-157-annual-maintenance-portable-fire-extinguishers | annual maintenance check | Annual maintenance | https://www.ecfr.gov/current/title-29/subtitle-B/chapter-XVII/part-1910/subpart-L/section-1910.157 | The employer shall assure that portable fire extinguishers are subjected to an annual maintenance check. Stored pressure extinguishers do not require an internal examination. The employer shall record the annual maintenance date and retain this record for one year after the last entry or the life of the shell, whicheve... | https://referencesource.org/fire-extinguisher-inspection-testing-intervals-by-type/osha-29-cfr-1910-157-annual-maintenance-portable-fire-extinguishers/ | [
"agent_type",
"interval"
] | null |
Aqueous Film Forming foam (AFFF) | OSHA 29 CFR 1910.157 | Table L-1 | [
"authority",
"obligation"
] | osha-29-cfr-1910-157-hydrostatic-test-aqueous-film-forming-foam-afff | 5 | Hydrostatic test | https://www.ecfr.gov/current/title-29/subtitle-B/chapter-XVII/part-1910/subpart-L/section-1910.157 | The employer shall assure that portable extinguishers are hydrostatically tested at the intervals listed in Table L-1 of this section, except under any of the following conditions: ( i ) When the unit has been repaired by soldering, welding, brazing, or use of patching compounds; ( ii ) When the cylinder or shell threa... | https://referencesource.org/fire-extinguisher-inspection-testing-intervals-by-type/osha-29-cfr-1910-157-hydrostatic-test-aqueous-film-forming-foam-afff/ | [
"agent_type",
"citation",
"interval"
] | null |
Carbon dioxide | OSHA 29 CFR 1910.157 | Table L-1 | [
"authority",
"obligation"
] | osha-29-cfr-1910-157-hydrostatic-test-carbon-dioxide | 5 | Hydrostatic test | https://www.ecfr.gov/current/title-29/subtitle-B/chapter-XVII/part-1910/subpart-L/section-1910.157 | The employer shall assure that portable extinguishers are hydrostatically tested at the intervals listed in Table L-1 of this section, except under any of the following conditions: ( i ) When the unit has been repaired by soldering, welding, brazing, or use of patching compounds; ( ii ) When the cylinder or shell threa... | https://referencesource.org/fire-extinguisher-inspection-testing-intervals-by-type/osha-29-cfr-1910-157-hydrostatic-test-carbon-dioxide/ | [
"agent_type",
"citation",
"interval"
] | null |
Cartridge operated water and/or antifreeze | OSHA 29 CFR 1910.157 | Table L-1 | [
"authority",
"obligation"
] | osha-29-cfr-1910-157-hydrostatic-test-cartridge-operated-water-and-or-antifreeze | 5 | Hydrostatic test | https://www.ecfr.gov/current/title-29/subtitle-B/chapter-XVII/part-1910/subpart-L/section-1910.157 | The employer shall assure that portable extinguishers are hydrostatically tested at the intervals listed in Table L-1 of this section, except under any of the following conditions: ( i ) When the unit has been repaired by soldering, welding, brazing, or use of patching compounds; ( ii ) When the cylinder or shell threa... | https://referencesource.org/fire-extinguisher-inspection-testing-intervals-by-type/osha-29-cfr-1910-157-hydrostatic-test-cartridge-operated-water-and-or-antifreeze/ | [
"agent_type",
"citation",
"interval"
] | null |
Halon 1211 | OSHA 29 CFR 1910.157 | Table L-1 | [
"authority",
"obligation"
] | osha-29-cfr-1910-157-hydrostatic-test-halon-1211 | 12 | Hydrostatic test | https://www.ecfr.gov/current/title-29/subtitle-B/chapter-XVII/part-1910/subpart-L/section-1910.157 | The employer shall assure that portable extinguishers are hydrostatically tested at the intervals listed in Table L-1 of this section, except under any of the following conditions: ( i ) When the unit has been repaired by soldering, welding, brazing, or use of patching compounds; ( ii ) When the cylinder or shell threa... | https://referencesource.org/fire-extinguisher-inspection-testing-intervals-by-type/osha-29-cfr-1910-157-hydrostatic-test-halon-1211/ | [
"agent_type",
"citation",
"interval"
] | null |
Halon 1301 | OSHA 29 CFR 1910.157 | Table L-1 | [
"authority",
"obligation"
] | osha-29-cfr-1910-157-hydrostatic-test-halon-1301 | 12 | Hydrostatic test | https://www.ecfr.gov/current/title-29/subtitle-B/chapter-XVII/part-1910/subpart-L/section-1910.157 | The employer shall assure that portable extinguishers are hydrostatically tested at the intervals listed in Table L-1 of this section, except under any of the following conditions: ( i ) When the unit has been repaired by soldering, welding, brazing, or use of patching compounds; ( ii ) When the cylinder or shell threa... | https://referencesource.org/fire-extinguisher-inspection-testing-intervals-by-type/osha-29-cfr-1910-157-hydrostatic-test-halon-1301/ | [
"agent_type",
"citation",
"interval"
] | null |
Loaded stream | OSHA 29 CFR 1910.157 | Table L-1 | [
"authority",
"obligation"
] | osha-29-cfr-1910-157-hydrostatic-test-loaded-stream | 5 | Hydrostatic test | https://www.ecfr.gov/current/title-29/subtitle-B/chapter-XVII/part-1910/subpart-L/section-1910.157 | The employer shall assure that portable extinguishers are hydrostatically tested at the intervals listed in Table L-1 of this section, except under any of the following conditions: ( i ) When the unit has been repaired by soldering, welding, brazing, or use of patching compounds; ( ii ) When the cylinder or shell threa... | https://referencesource.org/fire-extinguisher-inspection-testing-intervals-by-type/osha-29-cfr-1910-157-hydrostatic-test-loaded-stream/ | [
"agent_type",
"citation",
"interval"
] | null |
Dry chemical, stored pressure | OSHA 29 CFR 1910.157 | Table L-1 | [
"authority",
"obligation"
] | osha-29-cfr-1910-157-hydrostatic-test-mild-steel-brazed-brass-or-aluminum-shells-dry-chemical-stored-pressure | 12 | Hydrostatic test | https://www.ecfr.gov/current/title-29/subtitle-B/chapter-XVII/part-1910/subpart-L/section-1910.157 | The employer shall assure that portable extinguishers are hydrostatically tested at the intervals listed in Table L-1 of this section, except under any of the following conditions: ( i ) When the unit has been repaired by soldering, welding, brazing, or use of patching compounds; ( ii ) When the cylinder or shell threa... | https://referencesource.org/fire-extinguisher-inspection-testing-intervals-by-type/osha-29-cfr-1910-157-hydrostatic-test-mild-steel-brazed-brass-or-aluminum-shells-dry-chemical-stored-pressure/ | [
"agent_type",
"citation",
"interval",
"shell_material"
] | mild steel, brazed brass or aluminum shells |
Dry chemical, cartridge or cylinder operated | OSHA 29 CFR 1910.157 | Table L-1 | [
"authority",
"obligation"
] | osha-29-cfr-1910-157-hydrostatic-test-mild-steel-shells-dry-chemical-cartridge-or-cylinder-operated | 12 | Hydrostatic test | https://www.ecfr.gov/current/title-29/subtitle-B/chapter-XVII/part-1910/subpart-L/section-1910.157 | The employer shall assure that portable extinguishers are hydrostatically tested at the intervals listed in Table L-1 of this section, except under any of the following conditions: ( i ) When the unit has been repaired by soldering, welding, brazing, or use of patching compounds; ( ii ) When the cylinder or shell threa... | https://referencesource.org/fire-extinguisher-inspection-testing-intervals-by-type/osha-29-cfr-1910-157-hydrostatic-test-mild-steel-shells-dry-chemical-cartridge-or-cylinder-operated/ | [
"agent_type",
"citation",
"interval",
"shell_material"
] | mild steel shells |
Dry powder, cartridge or cylinder operated | OSHA 29 CFR 1910.157 | Table L-1 | [
"authority",
"obligation"
] | osha-29-cfr-1910-157-hydrostatic-test-mild-steel-shells-dry-powder-cartridge-or-cylinder-operated | 12 | Hydrostatic test | https://www.ecfr.gov/current/title-29/subtitle-B/chapter-XVII/part-1910/subpart-L/section-1910.157 | The employer shall assure that portable extinguishers are hydrostatically tested at the intervals listed in Table L-1 of this section, except under any of the following conditions: ( i ) When the unit has been repaired by soldering, welding, brazing, or use of patching compounds; ( ii ) When the cylinder or shell threa... | https://referencesource.org/fire-extinguisher-inspection-testing-intervals-by-type/osha-29-cfr-1910-157-hydrostatic-test-mild-steel-shells-dry-powder-cartridge-or-cylinder-operated/ | [
"agent_type",
"citation",
"interval",
"shell_material"
] | mild steel shells |
Dry chemical | OSHA 29 CFR 1910.157 | Table L-1 | [
"authority",
"obligation"
] | osha-29-cfr-1910-157-hydrostatic-test-stainless-steel-dry-chemical | 5 | Hydrostatic test | https://www.ecfr.gov/current/title-29/subtitle-B/chapter-XVII/part-1910/subpart-L/section-1910.157 | The employer shall assure that portable extinguishers are hydrostatically tested at the intervals listed in Table L-1 of this section, except under any of the following conditions: ( i ) When the unit has been repaired by soldering, welding, brazing, or use of patching compounds; ( ii ) When the cylinder or shell threa... | https://referencesource.org/fire-extinguisher-inspection-testing-intervals-by-type/osha-29-cfr-1910-157-hydrostatic-test-stainless-steel-dry-chemical/ | [
"agent_type",
"citation",
"interval",
"shell_material"
] | stainless steel |
Foam | OSHA 29 CFR 1910.157 | Table L-1 | [
"authority",
"obligation"
] | osha-29-cfr-1910-157-hydrostatic-test-stainless-steel-shell-foam | 5 | Hydrostatic test | https://www.ecfr.gov/current/title-29/subtitle-B/chapter-XVII/part-1910/subpart-L/section-1910.157 | The employer shall assure that portable extinguishers are hydrostatically tested at the intervals listed in Table L-1 of this section, except under any of the following conditions: ( i ) When the unit has been repaired by soldering, welding, brazing, or use of patching compounds; ( ii ) When the cylinder or shell threa... | https://referencesource.org/fire-extinguisher-inspection-testing-intervals-by-type/osha-29-cfr-1910-157-hydrostatic-test-stainless-steel-shell-foam/ | [
"agent_type",
"citation",
"interval",
"shell_material"
] | stainless steel shell |
Soda acid | OSHA 29 CFR 1910.157 | Table L-1 | [
"authority",
"obligation"
] | osha-29-cfr-1910-157-hydrostatic-test-stainless-steel-shell-soda-acid | 5 | Hydrostatic test | https://www.ecfr.gov/current/title-29/subtitle-B/chapter-XVII/part-1910/subpart-L/section-1910.157 | The employer shall assure that portable extinguishers are hydrostatically tested at the intervals listed in Table L-1 of this section, except under any of the following conditions: ( i ) When the unit has been repaired by soldering, welding, brazing, or use of patching compounds; ( ii ) When the cylinder or shell threa... | https://referencesource.org/fire-extinguisher-inspection-testing-intervals-by-type/osha-29-cfr-1910-157-hydrostatic-test-stainless-steel-shell-soda-acid/ | [
"agent_type",
"citation",
"interval",
"shell_material"
] | stainless steel shell |
Stored pressure water and/or antifreeze | OSHA 29 CFR 1910.157 | Table L-1 | [
"authority",
"obligation"
] | osha-29-cfr-1910-157-hydrostatic-test-stored-pressure-water-and-or-antifreeze | 5 | Hydrostatic test | https://www.ecfr.gov/current/title-29/subtitle-B/chapter-XVII/part-1910/subpart-L/section-1910.157 | The employer shall assure that portable extinguishers are hydrostatically tested at the intervals listed in Table L-1 of this section, except under any of the following conditions: ( i ) When the unit has been repaired by soldering, welding, brazing, or use of patching compounds; ( ii ) When the cylinder or shell threa... | https://referencesource.org/fire-extinguisher-inspection-testing-intervals-by-type/osha-29-cfr-1910-157-hydrostatic-test-stored-pressure-water-and-or-antifreeze/ | [
"agent_type",
"citation",
"interval"
] | null |
Wetting agent | OSHA 29 CFR 1910.157 | Table L-1 | [
"authority",
"obligation"
] | osha-29-cfr-1910-157-hydrostatic-test-wetting-agent | 5 | Hydrostatic test | https://www.ecfr.gov/current/title-29/subtitle-B/chapter-XVII/part-1910/subpart-L/section-1910.157 | The employer shall assure that portable extinguishers are hydrostatically tested at the intervals listed in Table L-1 of this section, except under any of the following conditions: ( i ) When the unit has been repaired by soldering, welding, brazing, or use of patching compounds; ( ii ) When the cylinder or shell threa... | https://referencesource.org/fire-extinguisher-inspection-testing-intervals-by-type/osha-29-cfr-1910-157-hydrostatic-test-wetting-agent/ | [
"agent_type",
"citation",
"interval"
] | null |
Dry chemical extinguishers having non-refillable disposable containers | OSHA 29 CFR 1910.157 | null | [
"authority",
"obligation"
] | osha-29-cfr-1910-157-internal-examination-dry-chemical-extinguishers-having-non-refillable-disposable-containers | exempt from this requirement | Internal examination | https://www.ecfr.gov/current/title-29/subtitle-B/chapter-XVII/part-1910/subpart-L/section-1910.157 | The employer shall assure that stored pressure dry chemical extinguishers that require a 12-year hydrostatic test are emptied and subjected to applicable maintenance procedures every 6 years. Dry chemical extinguishers having non-refillable disposable containers are exempt from this requirement. When recharging or hydr... | https://referencesource.org/fire-extinguisher-inspection-testing-intervals-by-type/osha-29-cfr-1910-157-internal-examination-dry-chemical-extinguishers-having-non-refillable-disposable-containers/ | [
"agent_type",
"interval"
] | null |
stored pressure dry chemical extinguishers that require a 12-year hydrostatic test | OSHA 29 CFR 1910.157 | null | [
"authority",
"obligation"
] | osha-29-cfr-1910-157-internal-examination-stored-pressure-dry-chemical-extinguishers-that-require-a-12-year-hydrostatic-te | every 6 years | Internal examination | https://www.ecfr.gov/current/title-29/subtitle-B/chapter-XVII/part-1910/subpart-L/section-1910.157 | The employer shall assure that stored pressure dry chemical extinguishers that require a 12-year hydrostatic test are emptied and subjected to applicable maintenance procedures every 6 years. Dry chemical extinguishers having non-refillable disposable containers are exempt from this requirement. When recharging or hydr... | https://referencesource.org/fire-extinguisher-inspection-testing-intervals-by-type/osha-29-cfr-1910-157-internal-examination-stored-pressure-dry-chemical-extinguishers-that-require-a-12-year-hydrostatic-te/ | [
"agent_type",
"interval"
] | null |
Portable extinguishers | OSHA 29 CFR 1910.157 | null | [
"authority",
"obligation"
] | osha-29-cfr-1910-157-monthly-visual-inspection-portable-extinguishers | monthly | Monthly visual inspection | https://www.ecfr.gov/current/title-29/subtitle-B/chapter-XVII/part-1910/subpart-L/section-1910.157 | Portable extinguishers or hose used in lieu thereof under <https://www.ecfr.gov/current/title-29/section-1910.157#p-1910.157(d)(3)> paragraph (d)(3) of this section shall be visually inspected monthly. | https://referencesource.org/fire-extinguisher-inspection-testing-intervals-by-type/osha-29-cfr-1910-157-monthly-visual-inspection-portable-extinguishers/ | [
"agent_type",
"interval"
] | null |
Fire extinguisher inspection, maintenance and hydrostatic test intervals by agent type
Canonical, always-current version: https://referencesource.org/fire-extinguisher-inspection-testing-intervals-by-type/ Machine-readable: https://referencesource.org/fire-extinguisher-inspection-testing-intervals-by-type/data.json — this mirror is a point-in-time copy.
- Last verified: 2026-08-19
- Stale after: 2027-08-19 (past this date, prefer the canonical copy — it re-verifies on a cadence this snapshot does not)
- Records: 34
NFPA 10 sets four separate service obligations for a portable fire extinguisher (monthly visual inspection, annual maintenance, periodic internal examination, and hydrostatic pressure testing) and the interval for two of those four depends on which agent and shell the extinguisher is, in a way that is scattered across several sections and a table rather than stated as one list. A record here is one obligation for one extinguisher type/shell combination, with the interval and the NFPA 10 section it comes from. Answers 'how often does a CO2 extinguisher need hydrostatic testing', 'does a stainless steel dry chemical extinguisher get the same 12-year hydro interval as a standard one', 'how often does a wet chemical K-class extinguisher need internal examination', and 'my dry chemical extinguisher is nonrechargeable, when does it get replaced instead of retested'. The exceptions are where a facility manager gets this wrong: stainless steel dry chemical shells get the 5-year interval that pressurized-water and CO2 units get, not the 12-year interval every other dry chemical extinguisher gets, and nonrechargeable stored-pressure extinguishers skip hydrostatic testing entirely in favor of a hard 12-year removal-from-service date. Two authorities are carried side by side, because a US workplace is answerable to both and they are not word-for-word identical: NFPA 10, as restated for regulated facilities by the Minnesota Department of Health, and OSHA's own general-industry standard at 29 CFR 1910.157, whose Table L-1 sets hydrostatic intervals directly in regulation and names types the NFPA summary does not (foam, AFFF, Halon 1211 and 1301, dry powder, wetting agent). Where the two overlap they agree, and each row says which rulebook it answers to.
Provenance — what every record carries
Every record carries source (the URL the value was read from) and
source_quote (a verbatim quote from that page stating it). A value you
cannot check against its page is indistinguishable from an invented one;
these can all be checked. Each record is also individually addressable on
the canonical site at its url.
Licence position
NFPA 10 is a copyrighted, sold standard; the facts (which interval applies to which extinguisher type) are not themselves copyrightable and are already restated by every state health/fire authority that regulates against it. This asset never reproduces the standard's text. The NFPA-derived rows take the interval and its qualifier from a Minnesota Department of Health guidance document that already restates NFPA 10's requirements for its regulated facilities, quote a short verbatim span, and cite the specific NFPA 10 section. The OSHA rows are taken from 29 CFR 1910.157, which is a US government work in the public domain and states its own intervals in Table L-1 rather than incorporating NFPA 10 by reference.
Facts are not copyrightable; what this dataset takes from each source is a fact plus a short attributed quote linking back to the page that states it.
Sources
- https://www.health.state.mn.us/facilities/regulation/engineering/docs/lscfireext.pdf
- https://www.ecfr.gov/current/title-29/subtitle-B/chapter-XVII/part-1910/subpart-L/section-1910.157