maintenance_question
string
missing_required_steps
list
false
[ "Turn the unit off at the thermostat.", "Open the access panel, remove visible debris from the pan and drain opening, and use a manufacturer-approved, non-damaging method to clear the blockage.", "Flush the drain with clean water and confirm that it discharges freely without leaks.", "Refit the panel, restore...
{ "required_steps": [ { "step_order": 1, "instruction": "Shut down the unit, isolate the electrical supply, apply lockout/tagout, and verify that moving components have stopped before opening the access panel." }, { "step_order": 2, "instruction": "Inspect the condensate pan and dr...
[ "The answer directs opening the access panel without requiring electrical isolation and lockout/tagout first." ]
0.75
[ { "candidate_step_order": 1, "result": "部分符合", "reference_step_orders": [ 1 ], "explanation": "Turning the unit off at the thermostat is a shutdown action, but it does not establish electrical isolation, lockout/tagout, or a verified stop before access." }, { "candidate_step_order"...
The drain-clearing and post-maintenance checks are substantially covered, but the answer omits the required electrical isolation and lockout/tagout before opening the unit. It does not pass because of this safety-critical omission.
What steps are required to clear and check a blocked condensate drain on a fan-coil unit?
[ "Isolate the electrical supply, apply lockout/tagout, and verify that moving components have stopped before opening the access panel." ]
false
[ "Stop the fan at the local controller and remove the guard while the electrical supply remains connected.", "Replace the belt with the specified belt, align the pulleys, and set tension according to the manufacturer's instructions.", "Reinstall the guard, restore power, and observe operation from a safe positio...
{ "required_steps": [ { "step_order": 1, "instruction": "Stop the fan, isolate its electrical supply, and apply lockout/tagout before accessing the drive assembly." }, { "step_order": 2, "instruction": "Verify that the fan and drive have come to a complete stop before opening the g...
[ "The answer directs removal of the drive guard while the electrical supply remains connected.", "The answer does not require verifying a complete stop before accessing the drive assembly." ]
0.6
[ { "candidate_step_order": 1, "result": "不符合", "reference_step_orders": [ 1, 2 ], "explanation": "The step explicitly leaves the electrical supply connected while removing the guard and does not require confirming that the drive has stopped." }, { "candidate_step_order": 2, ...
The belt specification and adjustment guidance, guard reinstallation, and final observation are covered. However, the answer explicitly permits access while the supply remains connected and omits confirmation that the drive has stopped, creating critical safety violations.
How should a drive belt be replaced on an air-handling unit fan?
[ "Isolate the electrical supply and apply lockout/tagout before accessing the drive assembly.", "Verify that the fan and drive have completely stopped before opening the guard." ]
false
[ "Turn the unit off at the thermostat and wait for the fan to stop.", "Remove the dirty filter, inspect the rack, and install the specified replacement with its airflow arrow aligned with the unit's airflow direction.", "Secure the access panel, restore power, and confirm normal airflow with no alarms." ]
{ "required_steps": [ { "step_order": 1, "instruction": "Shut down the unit, isolate its electrical supply, apply lockout/tagout, and verify that the fan has stopped before opening the access panel." }, { "step_order": 2, "instruction": "Remove the used filter, check that the rack ...
[ "The answer does not require electrical isolation and lockout/tagout before access to the unit." ]
0.75
[ { "candidate_step_order": 1, "result": "部分符合", "reference_step_orders": [ 1 ], "explanation": "Turning the unit off and waiting for the fan to stop addresses shutdown, but the answer omits electrical isolation, lockout/tagout, and verification before panel access." }, { "candidate_...
The answer covers filter selection, installation, panel closure, and post-maintenance checks, but it omits a critical isolation and lockout/tagout requirement before access. It therefore does not pass.
What is the safe procedure for replacing the return-air filter in an air-handling unit?
[ "Isolate the electrical supply, apply lockout/tagout, and verify the fan has stopped before opening the access panel." ]

HVAC Maintenance Procedure Answer Verification Dataset

Designed for evaluating maintenance question answering for industrial HVAC equipment, this dataset records maintenance questions, candidate action steps, and structured procedure references covering step order, prerequisites, and safety restrictions. It also provides step-by-step mappings, missing requirements, safety violations, completeness scores, and overall assessments. These records support automated evaluation of answer completeness, procedural compliance, and safety, as well as system improvement and benchmarking.

Technical Specifications

Field Type Description
overall_pass boolean Indicates whether the answer is complete and complies with the procedure and applicable safety restrictions.
candidate_steps array The proposed maintenance action steps, recorded in the order given in the answer under evaluation.
procedure_basis object The procedure steps, prerequisites, and safety restrictions used to verify the answer.
safety_violations array Safety restrictions that the answer under evaluation violates or may violate.
completeness_score number Measures how fully the answer covers applicable procedure requirements, on a scale from 0 to 1.
evaluation_details array Records how each candidate action step corresponds to procedure requirements and explains the evaluation rationale.
overall_assessment string Summarizes answer completeness, procedural compliance, and reasons for any failure.
maintenance_question string The industrial HVAC equipment maintenance question to be answered.
missing_required_steps array Procedure steps or other required elements not covered by the answer under evaluation.

Compliance Statement

Authorization TypeCC-BY-NC-SA 4.0 (Attribution–NonCommercial–ShareAlike)
Commercial UseRequires exclusive subscription or authorization contract (monthly or per-invocation charging)
Privacy and AnonymizationNo PII, no real company names, simulated scenarios follow industry standards
Compliance SystemCompliant with China's Data Security Law / EU GDPR / supports enterprise data access logs

Source & Contact

contact@mobiusi.com

Downloads last month
12