chunk_id large_string | report_id large_string | text large_string |
|---|---|---|
GD-20260056_0 | GD-20260056 | Report GD-20260056 | MI | 2026 | GAS DISTRIBUTION | OTHER INCIDENT CAUSE
Extracted: severity_weak_label=severe
Narrative: ON JULY 28, 2026, A NATURAL GAS-FUELED EXPLOSION AND SUBSEQUENT FIRE OCCURRED AT A COMMERCIAL BUILDING LOCATED AT 69608 SUNSET BOULEVARD, UNION, MICHIGAN, RESULTING IN INJURY TO ONE INDIVIDUAL. EVID... |
GD-20260053_0 | GD-20260053 | Report GD-20260053 | WI | 2026 | GAS DISTRIBUTION | OTHER OUTSIDE FORCE DAMAGE
Extracted: severity_weak_label=moderate
Narrative: AS EXCERPTED FROM PRESS RELEASE FROM WALWORTH COUNTY SHERIFF'S DEPARTMENT WHICH STATES, IN PART: "AT APPROXIMATELY 3:09 AM ON JULY 18, 2026, THE WALWORTH COUNTY SHERIFF'S OFFICE COMMUNICAT... |
GD-20260055_0 | GD-20260055 | Report GD-20260055 | ND | 2026 | GAS DISTRIBUTION | EXCAVATION DAMAGE
Extracted: severity_weak_label=severe
Narrative: ON JULY 15, 2026, AT APPROXIMATELY 12:07 PM CENTRAL, MONTANA DAKOTA UTILITIES CO. (MDU) RECEIVED NOTIFICATION OF A SERVICE LINE STRIKE AT 1404 4TH AVE WEST IN WILLISTON, NORTH DAKOTA. UPON A SERVICE TE... |
GD-20260050_0 | GD-20260050 | Report GD-20260050 | MI | 2026 | GAS DISTRIBUTION | OTHER INCIDENT CAUSE
Extracted: severity_weak_label=moderate
Narrative: EXPLOSION AT 956 FULTON STREET WEST GRAND RAPIDS MI. CAUSE IS CURRENTLY UNKNOWN AND BEING INVESTIGATED. |
GD-20260051_0 | GD-20260051 | Report GD-20260051 | OH | 2026 | GAS DISTRIBUTION | EXCAVATION DAMAGE
Extracted: severity_weak_label=moderate
Narrative: ON JUNE 26, 2026, AT APPROXIMATELY 2:58 P.M., ENBRIDGE GAS OHIO DISPATCH RECEIVED NOTIFICATION OF A REPORTED PIPELINE DAMAGE EVENT AT 3787 N. RIDGE ROAD, PERRY, OHIO 44081. THE INCIDENT INVOLVED A TH... |
GD-20260048_0 | GD-20260048 | Report GD-20260048 | OH | 2026 | GAS DISTRIBUTION | EXCAVATION DAMAGE
Extracted: severity_weak_label=moderate
Narrative: ON JUNE 25, 2026, AT APPROXIMATELY 3:33 P.M., ENBRIDGE GAS OHIO WAS NOTIFIED BY THE TWINSBURG FIRE DEPARTMENT THAT A GAS LINE HAD BEEN STRUCK NEAR 2146 HIRAM LANE, TWINSBURG/HUDSON, OHIO 44236. AN EN... |
GD-20260048_1 | GD-20260048 | Report GD-20260048 | OH | 2026 | GAS DISTRIBUTION | EXCAVATION DAMAGE
Extracted: severity_weak_label=moderate
Narrative: FACTOR INVOLVING BENCHMARK, ENBRIDGE GAS OHIO'S CONTRACT LOCATING PROVIDER. BENCHMARK’S MARKS WERE 2 FEET 4 INCHES AWAY FROM THE 2-INCH PIPELINE AT THE POINT OF DAMAGE, PUTTING IT 9 INCHES OUTSIDE TH... |
GD-20260049_0 | GD-20260049 | Report GD-20260049 | ND | 2026 | GAS DISTRIBUTION | EXCAVATION DAMAGE
Extracted: severity_weak_label=minor
Narrative: ON 06/24/2026 IN DICKINSON, NORTH DAKOTA, A CITY-HIRED CONTRACTOR DAMAGED MONTANA DAKOTA UTILITIES’ (MDU’S) 12-INCH HIGH-PRESSURE HDPE GAS MAIN DURING EXCAVATION ACTIVITIES ASSOCIATED WITH WATER, SEWER,... |
GD-20260047_0 | GD-20260047 | Report GD-20260047 | IL | 2026 | GAS DISTRIBUTION | OTHER INCIDENT CAUSE
Extracted: severity_weak_label=severe
Narrative: AT APPROXIMATELY 06:10 HOURS CST ON MONDAY, JUNE 22, 2026, AN EXPLOSION OCCURRED AT A MOBILE HOME LOCATED AT 1506 ESTATES ROAD IN THE CHATEAU ESTATES MANUFACTURED HOME COMMUNITY IN DIXON, ILLINOIS. ... |
GD-20260047_1 | GD-20260047 | Report GD-20260047 | IL | 2026 | GAS DISTRIBUTION | OTHER INCIDENT CAUSE
Extracted: severity_weak_label=severe
Narrative: ALL METERS IN THE CHATEAU ESTATES COMMUNITY ON JUNE 25, 2026. UPON INFORMATION AND BELIEF, THE OCCUPANT AT 1506 ESTATES ROAD SUSTAINED BURN INJURIES AND WAS TRANSPORTED TO A HOSPITAL IN ROCKFORD, IL... |
GD-20260046_0 | GD-20260046 | Report GD-20260046 | TX | 2026 | GAS DISTRIBUTION | EXCAVATION DAMAGE
Extracted: severity_weak_label=critical
Narrative: THIS REPORT REFLECTS PRELIMINARY INFORMATION. THE INVESTIGATION, TO WHICH THE RAILROAD COMMISSION OF TEXAS AND PHMSA ARE PARTIES, IS ONGOING UNDER THE DIRECTION OF THE NATIONAL TRANSPORTATION SAFETY ... |
GD-20260045_0 | GD-20260045 | Report GD-20260045 | CA | 2026 | GAS DISTRIBUTION | OTHER OUTSIDE FORCE DAMAGE
Extracted: severity_weak_label=minor
Narrative: ON 05/20/2026, SOCALGAS RESPONDED TO AN EXCAVATION INCIDENT. THE INITIAL REPORT INDICATED THAT A THIRD-PARTY CONTRACTOR MAY HAVE STRUCK A 6-IN STEEL GAS MAIN WITH GRADING EQUIPMENT DURING BACKF... |
GD-20260044_0 | GD-20260044 | Report GD-20260044 | LA | 2026 | GAS DISTRIBUTION | EXCAVATION DAMAGE
Extracted: severity_weak_label=severe
Narrative: ATMOS ENERGY'S FACILITY WAS DAMAGED BY A THIRD-PARTY EXCAVATOR. NO LOCATE TICKET REQUEST WAS SUBMITTED FOR THE EXCAVATION. ATMOS ENERGY WAS NOTIFIED OF THE DAMAGE AT 8:08 AM ON MAY 20, 2026. AN ATMOS E... |
GD-20260041_0 | GD-20260041 | Report GD-20260041 | WV | 2026 | GAS DISTRIBUTION | OTHER OUTSIDE FORCE DAMAGE
Extracted: severity_weak_label=severe
Narrative: ON MAY 18, AT APPROXIMATELY 14:00 HOURS THERE WAS A FIRE AT 21 NOLTE LANE, PROCTOR, WEST VIRGINIA 26055. THE INCIDENT IS STILL UNDER ACTIVE INVESTIGATION BY MULTIPLE PARTIES. HOPE GAS, INC... |
GD-20260043_0 | GD-20260043 | Report GD-20260043 | OH | 2026 | GAS DISTRIBUTION | OTHER OUTSIDE FORCE DAMAGE
Extracted: severity_weak_label=moderate
Narrative: AT APPROXIMATELY 15:55 ON 5-16-2026, ENBRIDGE GAS RECEIVED A CALL THAT THERE WAS A FIRE/EXPLOSION AT A THREE-UNIT APARTMENT COMPLEX WITH THE ADDRESSES 719, 721 AND 723 FIFTH ST, BELPRE, OH. ... |
GD-20260042_0 | GD-20260042 | Report GD-20260042 | NC | 2026 | GAS DISTRIBUTION | EXCAVATION DAMAGE
Extracted: severity_weak_label=moderate
Narrative: ON MAY 13TH, 2026 AT APPROXIMATELY 12:14PM, A NATURAL GAS INCIDENT/FIRE OCCURRED AT 5121 MORNING WOOD DRIVE IN MATTHEWS, NC. THE EVENT INVOLVED DAMAGE TO AN 8-INCH PLASTIC NATURAL GAS DISTRIBUTION MA... |
GD-20260040_0 | GD-20260040 | Report GD-20260040 | OH | 2026 | GAS DISTRIBUTION | EXCAVATION DAMAGE
Extracted: severity_weak_label=moderate
Narrative: ON 4-30-26 AT APPROX. 9:43 A.M., ENBRIDGE GAS OHIO RECEIVED A CALL FROM THE GIRARD FIRE DEPARTMENT THAT A GAS LINE WAS HIT NEAR 1018 N. STATE ST., IN GIRARD, OHIO 44420. WHILE IN ROUTE TO THE SCENE, ... |
GD-20260040_1 | GD-20260040 | Report GD-20260040 | OH | 2026 | GAS DISTRIBUTION | EXCAVATION DAMAGE
Extracted: severity_weak_label=moderate
Narrative: OF THE MAINLINE AT APPROX. 3:30 P.M. LEAK DETECTION SURVEYS WERE CONDUCTED AT 1022, 1020, AND 1018 N. STATE ST. AND ON GORDON ST. RESIDUAL GAS FROM THE DAMAGED MAINLINE WAS DETECTED AND MONITORED WIT... |
GD-20260038_0 | GD-20260038 | Report GD-20260038 | CA | 2026 | GAS DISTRIBUTION | OTHER OUTSIDE FORCE DAMAGE
Extracted: severity_weak_label=critical
Narrative: SOUTHWEST GAS (SWG) RESPONDED TO A RESIDENTIAL STRUCTURE FIRE FOLLOWING A DOMESTIC DISPUTE INVOLVING TWO INDIVIDUALS. THE INCIDENT RESULTED IN ONE MALE SUSTAINING STAB WOUNDS AND BEING HOSPI... |
GD-20260052_0 | GD-20260052 | Report GD-20260052 | CO | 2026 | GAS DISTRIBUTION | OTHER INCIDENT CAUSE
Extracted: severity_weak_label=severe
Narrative: ON APRIL 23, 2026 AT APPROXIMATELY 8:15PM A CALL WAS RECEIVED ON THE EMERGENCY MAINTENANCE LINE ABOUT A SMELL OF GAS AT LOT 72. A QUALIFIED MAINTENANCE STAFF PERSON WAS DISPATCHED TO INVESTIGATE AND... |
GD-20260037_0 | GD-20260037 | Report GD-20260037 | TX | 2026 | GAS DISTRIBUTION | OTHER INCIDENT CAUSE
Extracted: severity_weak_label=severe
Narrative: ON APRIL 21, 2026 AT APPROXIMATELY 6:04 P.M., THE CPS ENERGY SYSTEM OPERATOR RECEIVED CALLS FROM THE SAN ANTONIO FIRE DEPARTMENT INDICATING A STRUCTURE FIRE AT 15062 PRESTON HOLLOW DRIVE. AT APPROXI... |
GD-20260037_1 | GD-20260037 | Report GD-20260037 | TX | 2026 | GAS DISTRIBUTION | OTHER INCIDENT CAUSE
Extracted: severity_weak_label=severe
Narrative: NATURAL GAS MAY HAVE BEEN INVOLVED IN THE EXPLOSION. ACCORDINGLY, THE MANAGER CALLED IN ADDITIONAL PERSONNEL AND RELAYED THE INFORMATION TO THE DIRECTOR OF GAS CONSTRUCTION AND THE VICE PRESIDENT OF... |
GD-20260039_0 | GD-20260039 | Report GD-20260039 | OH | 2026 | GAS DISTRIBUTION | OTHER OUTSIDE FORCE DAMAGE
Extracted: severity_weak_label=moderate
Narrative: COLUMBIA GAS OF OHIO, INC. (COLUMBIA) ARRIVED ONSITE PER THE FIRE DEPARTMENT'S REQUEST AND MADE THE SITUATION SAFE. COLUMBIA FOUND THE METER SETTING AND RISER SUSTAINED HEAT AND FIRE DAMAGE... |
GD-20260036_0 | GD-20260036 | Report GD-20260036 | NC | 2026 | GAS DISTRIBUTION | INCORRECT OPERATION
Extracted: severity_weak_label=severe
Narrative: ON MONDAY, APRIL 20, 2026, TWO CONTRACTORS, WORKING ON BEHALF OF ENBRIDGE GAS NORTH CAROLINA (EGNC), WERE INJURED DUE TO ACCIDENTAL IGNITION OF NATURAL GAS WHILE PURGING A PLASTIC GAS MAIN IN A NEW ... |
GD-20260034_0 | GD-20260034 | Report GD-20260034 | GA | 2026 | GAS DISTRIBUTION | CORROSION FAILURE
Extracted: severity_weak_label=minor
Narrative: A GRADE 1 LEAK WAS DISCOVERED BY ROUTINE LEAKAGE SURVEY ON 3/30/2026. UPON EXCAVATING THE MAIN, COMPANY PERSONNEL NOTED THE WRAP COATING WAS DISBONDED IN THE AREA OF PINHOLE LEAK ON THE BOTTOMSIDE OF TH... |
GD-20260031_0 | GD-20260031 | Report GD-20260031 | MI | 2026 | GAS DISTRIBUTION | NATURAL FORCE DAMAGE
Extracted: severity_weak_label=moderate
Narrative: ON 3/21/26 AT 12:34, PIE&G ON CALL SUPERVISOR RECEIVED A CALL FROM OUR AFTER HOURS DISPATCH TO RESPOND TO A STRUCTURE FIRE ON CAULKINS LK RD. OUR SOUTH GAS STANDBY TECHNICIAN WAS IN THE FIELD WORK... |
GD-20260031_1 | GD-20260031 | Report GD-20260031 | MI | 2026 | GAS DISTRIBUTION | NATURAL FORCE DAMAGE
Extracted: severity_weak_label=moderate
Narrative: NORMAL IN AN EXPLOSION. TECH WAS DISPATCHED TO GO BACK TO THE SCENE AND INVESTIGATE FURTHER. TECH NOTED THERE WAS MORE DEBRIS IN THE YARD THAN HAD BEEN VISIBLE DURING THE INITIAL RESPONSE DUE TO T... |
GD-20260029_0 | GD-20260029 | Report GD-20260029 | TX | 2026 | GAS DISTRIBUTION | OTHER INCIDENT CAUSE
Extracted: severity_weak_label=severe
Narrative: ON MARCH 19, 2026, AT APPROXIMATELY 7:21 P.M., ATMOS ENERGY RECEIVED A NOTIFICATION OF A STRUCTURE FIRE AND AN EXPLOSION AT 620 MOSELEY IN LAKE DALLAS. THE FIRST ATMOS ENERGY TECHNICIAN ARRIVED ON T... |
GD-20260030_0 | GD-20260030 | Report GD-20260030 | CO | 2026 | GAS DISTRIBUTION | CORROSION FAILURE
Extracted: severity_weak_label=severe
Narrative: ON MARCH 19TH, 2026 AT APPROXIMATELY 11:45 AM MST, AN EXPLOSION OCCURRED WITHIN A COMMERCIAL BUILDING. FOLLOWING THE EXPLOSION, THE ADJACENT NATURAL GAS SERVICE LINE WAS EXCAVATED, AND THROUGH-WALL COR... |
GD-20260028_0 | GD-20260028 | Report GD-20260028 | CO | 2026 | GAS DISTRIBUTION | CORROSION FAILURE
Extracted: severity_weak_label=moderate
Narrative: ON MARCH 16, 2026, AT APPROXIMATELY 17:17 MST, AN EXPLOSION OCCURRED IN THE BASEMENT OF A RESIDENTIAL BUILDING ADJACENT TO A 1" NATURAL GAS DISTRIBUTION MAINLINE. EXCAVATION OF THE MAINLINE NEAR THE ... |
GD-20260032_0 | GD-20260032 | Report GD-20260032 | ID | 2026 | GAS DISTRIBUTION | OTHER INCIDENT CAUSE
Extracted: severity_weak_label=moderate
Narrative: ON THE MORNING OF 3/15/25 AT APPROXIMATELY 05:35 LOCAL TIME, AVISTA WAS NOTIFIED OF A FIRE AT THE RIVER CHURCH, 1687 E. HORSEHAVEN AVE. IN POST FALLS, IDAHO. A GAS FIRST RESPONDER WAS DISPATCHED A... |
GD-20260032_1 | GD-20260032 | Report GD-20260032 | ID | 2026 | GAS DISTRIBUTION | OTHER INCIDENT CAUSE
Extracted: severity_weak_label=moderate
Narrative: OF THE FACT. THESE TWO PEOPLE ASSEMBLED SUFFICIENT DETAILS TO MAKE THE REPORT TO THE NRC AT 11:10. THE METER/REGULATOR STILL NEED TO BE TESTED BY THIRD PARTY ENTITY TO DETERMINE IF THE NATURAL GAS... |
GD-20260027_0 | GD-20260027 | Report GD-20260027 | NJ | 2026 | GAS DISTRIBUTION | EXCAVATION DAMAGE
Extracted: severity_weak_label=moderate
Narrative: ON 3/4/2026 AT APPROXIMATELY 12:19 HRS PSEG WAS NOTIFIED OF A GAS IGNITION AND HOUSE EXPLOSION AT 86 MAGAZINE STREET NEWARK, NJ. PSEG ARRIVED ON SCENE AT 12:29 PM. FIRE AND POLICE WERE ONSITE. GAS W... |
GD-20260026_0 | GD-20260026 | Report GD-20260026 | MI | 2026 | GAS DISTRIBUTION | EXCAVATION DAMAGE
Extracted: severity_weak_label=minor
Narrative: ON MARCH 12, 2026, AT APPROXIMATELY 16:45, A CONSUMERS ENERGY GAS DISTRIBUTION CREW WAS PERFORMING EXCAVATION ACTIVITIES AT THE INTERSECTION OF BROWN ROAD AND GIDDINGS ROAD IN LAKE ORION, MICHIGAN (OAKL... |
GD-20260025_0 | GD-20260025 | Report GD-20260025 | OH | 2026 | GAS DISTRIBUTION | EXCAVATION DAMAGE
Extracted: severity_weak_label=minor
Narrative: COLUMBIA GAS OF OHIO INC. (COLUMBIA) RESPONDED TO A DISTRIBUTION MAIN LINE DAMAGE ON MARCH 9, 2026, AT 1093 FRANK RD. COLUMBUS, OHIO. THE OPERATOR FOUND THAT A BULLDOZER HAD STRUCK A PROPERLY MARKED MA... |
GD-20260021_0 | GD-20260021 | Report GD-20260021 | MO | 2026 | GAS DISTRIBUTION | NATURAL FORCE DAMAGE
Extracted: severity_weak_label=minor
Narrative: JACKSON, MISSOURI, RECEIVED APPROXIMATELY 4.7 INCHES OF RAINFALL OVER A 72-HOUR PERIOD, RESULTING IN SIGNIFICANT RUNOFF. THE VOLUME OF WATER OVERWHELMED A DRAINAGE DITCH OFF HIGHWAY 72, WHICH FEEDS... |
GD-20260022_0 | GD-20260022 | Report GD-20260022 | MO | 2026 | GAS DISTRIBUTION | EXCAVATION DAMAGE
Extracted: severity_weak_label=moderate
Narrative: WHILE DIRECTIONAL BORING, A THIRD-PARTY EXCAVATOR, BLACKWELL CONTRACTING, COMPLETELY SEVERED A 2- INCH PLASTIC MAIN LOCATED AT 5 WHITE HAVEN CT. THE LOCATE TICKET HAD NOT BEEN MARKED AS COMPLETE IN T... |
GD-20260023_0 | GD-20260023 | Report GD-20260023 | TX | 2026 | GAS DISTRIBUTION | INCORRECT OPERATION
Extracted: severity_weak_label=severe
Narrative: LAUREN SAMUELS LLC, A CONTRACTOR FOR CENTERPOINT ENERGY, WAS PERFORMING MAINTENANCE ACTIVITIES ON CENTERPOINT ENERGY FACILITIES. WHILE CONDUCTING A LEAK REPAIR ON A 2-INCH STEEL PIPELINE OPERATING AT... |
GD-20260020_0 | GD-20260020 | Report GD-20260020 | OH | 2026 | GAS DISTRIBUTION | OTHER OUTSIDE FORCE DAMAGE
Extracted: severity_weak_label=moderate
Narrative: AT APPROX. 22:00 ON 3-1-26, ENBRIDGE GAS RECEIVED A CALL THAT THERE WAS A FIRE/EXPLOSION AT 443 GARFIELD ST., YOUNGSTOWN, OH. AROUND 22:11 ENBRIDGE GAS WAS DISPATCHED TO THE SCENE AND ARRIVE... |
GD-20260020_1 | GD-20260020 | Report GD-20260020 | OH | 2026 | GAS DISTRIBUTION | OTHER OUTSIDE FORCE DAMAGE
Extracted: severity_weak_label=moderate
Narrative: INSURANCE CLAIM WAS PENDING. OPEN HOUSELINE GAS PIPING WAS OBSERVED IN THE BASEMEN WITH NO APPLIANCES PRESENT. METER DATA INDICATED GAS SERVICE WAS OFF BUT HAD BEEN TURNED BACK ON AT APPROX.... |
GD-20260019_0 | GD-20260019 | Report GD-20260019 | OH | 2026 | GAS DISTRIBUTION | OTHER INCIDENT CAUSE
Extracted: severity_weak_label=moderate
Narrative: ON 2-27-26 AT APPROX. 12:14 P.M., ENBRIDGE GAS OHIO RECEIVED A CALL ABOUT A POSSIBLE EXPLOSION AT 5914 CABLE AVE CLEVELAND, OHIO. ENBRIDGE GAS ARRIVED ONSITE ABOUT 12:54 P.M. AND FOUND AN ACTIVE F... |
GD-20260019_1 | GD-20260019 | Report GD-20260019 | OH | 2026 | GAS DISTRIBUTION | OTHER INCIDENT CAUSE
Extracted: severity_weak_label=moderate
Narrative: NO LEAKS. A JOINT SITE EXAMINATION ON 3-9-26 WAS LIMITED BY DEBRIS AT 5914 CABLE, WHICH PREVENTED SERVICE LINE TESTING AND ACCESS TO THE INSIDE METER. ENBRIDGE GAS RE-TESTED THE SERVICE LINE AT 59... |
GD-20260017_0 | GD-20260017 | Report GD-20260017 | MD | 2026 | GAS DISTRIBUTION | EXCAVATION DAMAGE
Extracted: severity_weak_label=severe
Narrative: ON FEBRUARY 27, 2026, AT APPROXIMATELY 10:27, A THIRD-PARTY CONTRACTOR CONDUCTING EXCAVATION ACTIVITIES STRUCK A 4-INCH SERVICE LINE LOCATED AT POWDER MILL ROAD AND CHERRY HILL ROAD IN BELTSVILLE, MARY... |
GD-20260017_1 | GD-20260017 | Report GD-20260017 | MD | 2026 | GAS DISTRIBUTION | EXCAVATION DAMAGE
Extracted: severity_weak_label=severe
Narrative: AND STANDARDS WERE ADEQUATE AND CLEARLY DEFINED THE REQUIRED CONTROLS FOR THIS TYPE OF OPERATION. THE EVENT WAS ATTRIBUTED TO A FAILURE TO FOLLOW AND ENFORCE ESTABLISHED REQUIREMENTS RATHER THAN DEFICI... |
GD-20260018_0 | GD-20260018 | Report GD-20260018 | MA | 2026 | GAS DISTRIBUTION | OTHER INCIDENT CAUSE
Extracted: severity_weak_label=severe
Narrative: TAUNTON PD CALLED TO REPORT A HOUSE FIRE AND POSSIBLE EXPLOSION AT THIS ADDRESS. EGMA TECHNICIANS, AND SUPERVISORS WERE DISPATCHED TO INVESTIGATE AND MAKE SAFE. UPON ARRIVAL, EVERSOURCE FOUND THE HO... |
GD-20260016_0 | GD-20260016 | Report GD-20260016 | GA | 2026 | GAS DISTRIBUTION | EXCAVATION DAMAGE
Extracted: severity_weak_label=minor
Narrative: A THIRD-PARTY PARTY EXCAVATOR (SHOOK CONSTRUCTION, A SUBCONTRACTOR FOR CABLE EAST LLC) STRUCK AND DAMAGED AN ATLANTA GAS LIGHT COMPANY (AGLC) 12-INCH STEEL GAS MAIN WHILE HORIZONTAL DIRECTIONALLY DRILLI... |
GD-20260015_0 | GD-20260015 | Report GD-20260015 | NY | 2026 | GAS DISTRIBUTION | OTHER OUTSIDE FORCE DAMAGE
Extracted: severity_weak_label=moderate
Narrative: THE LOCAL ELECTRIC UTILITY SUFFERED AN UNDERGROUND CABLE FAILURE. AS A RESULT OF THAT EVENT, OPERATOR PERSONNEL WERE CALLED TO THE SCENE AT 03:49 TO ASSIST FDNY WITH CO READS IN AN ADJACENT ... |
GD-20260014_0 | GD-20260014 | Report GD-20260014 | VA | 2026 | GAS DISTRIBUTION | OTHER INCIDENT CAUSE
Extracted: severity_weak_label=minor
Narrative: WASHINGTON GAS IS FULLY COOPERATING WITH THE NATIONAL TRANSPORTATION SAFETY BOARD (NTSB), WHICH HAS ASSUMED THE LEAD FOR THIS INVESTIGATION. WASHINGTON GAS WILL SUBMIT A SUPPLEMENTAL FILING, AS NECES... |
GD-20260012_0 | GD-20260012 | Report GD-20260012 | NH | 2026 | GAS DISTRIBUTION | OTHER INCIDENT CAUSE
Extracted: severity_weak_label=severe
Narrative: ON FEBRUARY 2, 2026, LIBERTY UTILITIES WAS NOTIFIED BY THE NASHUA FIRE DEPARTMENT OF AN INSIDE ODOR AT 440 AMHERST STREET, NASHUA, NEW HAMPSHIRE. LIBERTY UTILITIES RESPONDED AND CLOSED THE STREET VA... |
GD-20260011_0 | GD-20260011 | Report GD-20260011 | VA | 2026 | GAS DISTRIBUTION | OTHER INCIDENT CAUSE
Extracted: severity_weak_label=moderate
Narrative: ON FEBRUARY 1, 2026, A WASHINGTON GAS SERVICE TECHNICIAN WAS DISPATCHED TO 6411 GLADYS MAY LANE, ALEXANDRIA, VIRGINIA, TO INVESTIGATE A REPORTED GAS ODOR INSIDE A RESIDENCE. THE TECHNICIAN ARRIVED... |
GD-20260010_0 | GD-20260010 | Report GD-20260010 | MN | 2026 | GAS DISTRIBUTION | OTHER INCIDENT CAUSE
Extracted: severity_weak_label=critical
Narrative: REPORTS OF EXPLOSION AT 5064 JENNIFER CIRCLE. 911 CALL MADE AND REPORTED BY NEARBY RESIDENCE, 5096 JENNIFER CIRCLE, HERMANTOWN. FIRE ON STRUCTURE WHEN ARRIVED, GAS WAS SHUT OFF BY SQUEEZING SERV... |
GD-20260009_0 | GD-20260009 | Report GD-20260009 | WA | 2026 | GAS DISTRIBUTION | OTHER OUTSIDE FORCE DAMAGE
Extracted: severity_weak_label=moderate
Narrative: ON JANUARY 21, 2026, CNG RESPONDED TO A STRUCTURE FIRE/EXPLOSION AT 308 E SEATTLE AVE IN MOXEE, WA. CNG SERVICE MECHANIC ARRIVED ONSITE AND DISCOVERED NATURAL GAS IN THE SEWER. CNG PERSONNEL... |
GD-20260007_0 | GD-20260007 | Report GD-20260007 | IN | 2026 | GAS DISTRIBUTION | EXCAVATION DAMAGE
Extracted: severity_weak_label=moderate
Narrative: ON JANUARY 14, 2026, AT APPROXIMATELY 15:11, CENTERPOINT ENERGY (CNP) RECEIVED A NOTIFICATION THAT A FIBER INSTALLATION CREW HIT A GAS LINE WITH A BORING MACHINE AT 128 WOODHAVEN DRIVE, GREENCASTLE, ... |
GD-20260007_1 | GD-20260007 | Report GD-20260007 | IN | 2026 | GAS DISTRIBUTION | EXCAVATION DAMAGE
Extracted: severity_weak_label=moderate
Narrative: BASED UPON THE REPORT FROM THE FIRE DEPARTMENT, A GAS DETECTOR WAS UTILIZED, AND THE ONLY MEASURABLE LEL READING OCCURRED WHEN THE DETECTOR WAS PLACED DIRECTLY INTO THE HOLE WHERE THE BORING MACHINE ... |
GD-20260005_0 | GD-20260005 | Report GD-20260005 | VA | 2026 | GAS DISTRIBUTION | EXCAVATION DAMAGE
Extracted: severity_weak_label=minor
Narrative: ON JANUARY 5, 2026, AT APPROXIMATELY 10:53, GEOTHERMAL TECHNICAL, AN EXCAVATOR USING A 6” AUGER, STRUCK AN 8" MAIN LOCATED AT PACIFIC BLVD AND WAXPOOL ROAD, ASHBURN, VIRGINIA. WASHINGTON GAS WAS NOT... |
GD-20260024_0 | GD-20260024 | Report GD-20260024 | TX | 2025 | GAS DISTRIBUTION | EQUIPMENT FAILURE
Extracted: severity_weak_label=minor
Narrative: DECEMBER 28, 2025 - CIG REGULATION FAILURE OVER PRESSURIZED THE SYSTEM. DETERMINED THROUGH INVESTIGATION ON DECEMBER 29, 2025. VERIFIED THROUGH SCADA. DECEMBER 29, 2025 - TECHNICIAN, BRENT REHKOPF, RECE... |
GD-20260024_1 | GD-20260024 | Report GD-20260024 | TX | 2025 | GAS DISTRIBUTION | EQUIPMENT FAILURE
Extracted: severity_weak_label=minor
Narrative: AN OVERPRESSURE EVENT THAT OCCURRED. THIS EVENT IS REPORTABLE DUE TO THE AMOUNT OF GAS RELEASED. DUE TO A THUNDERSTORM, THE COMMUNICATION CONTROL BOX FOR THE REGULATOR WAS EFFECTED WHICH LED TO SCADA MA... |
GD-20260004_0 | GD-20260004 | Report GD-20260004 | PA | 2025 | GAS DISTRIBUTION | OTHER INCIDENT CAUSE
Extracted: severity_weak_label=critical
Narrative: ON DECEMBER 23, 2025, AT APPROXIMATELY 14:15 HOURS, AN EXPLOSION OCCURRED AT 905 TOWER RD, BRISTOL, PA. 3 FATALITIES AND AN ESTIMATED 20 INJURIES OCCURRED AS A RESULT OF THE INCIDENT. THIS INCID... |
GD-20260002_0 | GD-20260002 | Report GD-20260002 | CA | 2025 | GAS DISTRIBUTION | INCORRECT OPERATION
Extracted: severity_weak_label=severe
Narrative: ON DECEMBER 12, 2025, A SOCALGAS CREW WAS REMOVING AN OVERNIGHT PLUG DURING ROUTINE ABANDONMENT OPERATIONS. DURING THIS ACTIVITY, A RELEASE OF NATURAL GAS OCCURRED, AND AN EMPLOYEE WAS INJURED BY DEB... |
GD-20260003_0 | GD-20260003 | Report GD-20260003 | CA | 2025 | GAS DISTRIBUTION | EXCAVATION DAMAGE
Extracted: severity_weak_label=severe
Narrative: ON THURSDAY, DECEMBER 11, 2025, AT APPROXIMATELY 0938 HOURS, PG&E WAS NOTIFIED OF AN EXPLOSION AT 857/867 E. LEWELLING BLVD., HAYWARD, CA. A PG&E CREW WAS ON SITE MAKING REPAIRS TO A DIG-IN ON 3/4” STE... |
GD-20260001_0 | GD-20260001 | Report GD-20260001 | MN | 2025 | GAS DISTRIBUTION | OTHER OUTSIDE FORCE DAMAGE
Extracted: severity_weak_label=minor
Narrative: A VEHICLE LEFT THE ROADWAY OF CR 42 IN ALEXANDRIA, MN AND STRUCK A REGULATOR STATION CAUSING THE RELEASE OF NATURAL GAS. THIS INCIDENT WAS REPORTED ON 12/4/2025 BY 911 AT 2:47 AM. THIS RESULTED... |
GD-20250068_0 | GD-20250068 | Report GD-20250068 | FL | 2025 | GAS DISTRIBUTION | EXCAVATION DAMAGE
Extracted: severity_weak_label=critical
Narrative: ON THURSDAY, DECEMBER 4, 2025, PEOPLES GAS SYSTEM, INC. (PGS) WAS NOTIFIED OF A RUPTURED GAS LINE IN EUSTIS. PGS DOES NOT KNOW THE PRECISE TIME OF THE RUPTURE. HOWEVER, THE EUSTIS FIRE DEPARTMENT REC... |
GD-20250068_1 | GD-20250068 | Report GD-20250068 | FL | 2025 | GAS DISTRIBUTION | EXCAVATION DAMAGE
Extracted: severity_weak_label=critical
Narrative: GAS MAIN BUT FOUND NO EVIDENCE THAT THE EXCAVATOR DID SO. THE INVESTIGATION IS ONGOING, BUT THE CAUSE OF THE INCIDENT APPEARS TO BE THE EXCAVATOR’S FAILING TO MAINTAIN APPROPRIATE CLEARANCE FROM THE ... |
GD-20250069_0 | GD-20250069 | Report GD-20250069 | SD | 2025 | GAS DISTRIBUTION | OTHER OUTSIDE FORCE DAMAGE
Extracted: severity_weak_label=minor
Narrative: AT APPROXIMATELY 08:57 ON DECEMBER 3, 2025, SOUTH OF ABERDEEN SD, A VEHICLE SLID OFF AN ICY, GRAVEL ROAD STRIKING A 1" STEEL FARM TAP WITH A 4" STEEL BOLLARD BARRICADE IN THE RIGHT OF WAY. DRIV... |
GD-20250069_1 | GD-20250069 | Report GD-20250069 | SD | 2025 | GAS DISTRIBUTION | OTHER OUTSIDE FORCE DAMAGE
Extracted: severity_weak_label=minor
Narrative: OF ISOLATION WERE ORGANIZED AND COMPLETED; HOWEVER, GAS LOAD DEMANDS WERE A FACTOR IN EXECUTION DUE TO FRIGID WINTER WEATHER CONDITIONS. AT 18:33, WITH DIMINISHED GAS LOAD, THE DAMAGED FARM TAP... |
GD-20250066_0 | GD-20250066 | Report GD-20250066 | CO | 2025 | GAS DISTRIBUTION | EXCAVATION DAMAGE
Extracted: severity_weak_label=moderate
Narrative: ON DECEMBER 2, 2025, J&R TELCOM WAS PERFORMING A BORE TO INSTALL A NEW FIBER LINE ON GLEN HEATHER CT. DURING THE OPERATION, THE CREW STRUCK A 1-INCH POLYETHYLENE GAS SERVICE LINE SUPPLYING 917 GLEN H... |
GD-20250067_0 | GD-20250067 | Report GD-20250067 | CA | 2025 | GAS DISTRIBUTION | MATERIAL FAILURE OF PIPE OR WELD
Extracted: severity_weak_label=severe
Narrative: SOCALGAS CREWS RESPONDED TO A STRUCTURE FIRE AND EXPLOSION LOCATED AT 4222 SIERRA VISTA DR, CHINO HILLS. GAS HAS BEEN CONTROLLED AS OF 11/16/25 AT 10:31PM. THE INCIDENT WAS REPORTED TO T... |
GD-20250065_0 | GD-20250065 | Report GD-20250065 | KY | 2025 | GAS DISTRIBUTION | OTHER OUTSIDE FORCE DAMAGE
Extracted: severity_weak_label=minor
Narrative: ON 11/04/2025, A COMMERCIAL AIRCRAFT OPERATED BY UPS CRASHED AFTER TAKEOFF, CAUSING WIDESPREAD DAMAGE TO THE AREA. LOCATION INFORMATION PROVIDED IN THIS REPORT IS APPROXIMATE BASED ON AREA IMP... |
GD-20250064_0 | GD-20250064 | Report GD-20250064 | OH | 2025 | GAS DISTRIBUTION | EXCAVATION DAMAGE
Extracted: severity_weak_label=moderate
Narrative: ON NOVEMBER 3, 2025, COLUMBIA GAS OF OHIO, INC. (COLUMBIA) RESPONDED TO AN EMERGENCY ODOR CALL AT 586 EAST TOWN ST., COLUMBUS, OHIO AT THE REQUEST OF THE COLUMBUS FIRE DEPARTMENT. COLUMBIA’S FIRST R... |
GD-20250063_0 | GD-20250063 | Report GD-20250063 | HI | 2025 | GAS DISTRIBUTION | INCORRECT OPERATION
Extracted: severity_weak_label=severe
Narrative: ON FRIDAY 10/24/25, HAWAII GAS'S TRANSMISSION & DISTRIBUTION (T&D) DEPARTMENT RELOCATED A SECTION OF SYNTHETIC NATURAL GAS (SNG) COATED STEEL MAIN ON THE FORT SHAFTER MILITARY BASE. FORT SHAFTER REQU... |
GD-20250063_1 | GD-20250063 | Report GD-20250063 | HI | 2025 | GAS DISTRIBUTION | INCORRECT OPERATION
Extracted: severity_weak_label=severe
Narrative: THE HIGH-PRESSURE RISER. PERMANENT VALVES ARE NOT NORMALLY INSTALLED ON THE BYPASS TEE. A PERMANENT VALVE WOULD HAVE ELIMINATED THE NEED TO “CATCH LIVE GAS”. · ALTHOUGH HAWAII GAS HAS A PREVENTION OF... |
GD-20250063_2 | GD-20250063 | Report GD-20250063 | HI | 2025 | GAS DISTRIBUTION | INCORRECT OPERATION
Extracted: severity_weak_label=severe
Narrative: 12/31/25) · DETERMINE IF THERE IS AN OPPORTUNITY TO LEVERAGE OTHER BUSINESS UNITS (WHO SEE THE MSA MORE OFTEN) TO IDENTIFY UNSAFE CONDITIONS AND GENERATE A HAZARDOUS ID. PROVIDE TRAINING AS APPLICABL... |
GD-20250062_0 | GD-20250062 | Report GD-20250062 | OH | 2025 | GAS DISTRIBUTION | OTHER INCIDENT CAUSE
Extracted: severity_weak_label=severe
Narrative: CENTERPOINT ENERGY WAS CALLED TO 608 FLORENCE AVE IN BELLEFONTAINE FOR A FIRE AT THE RESIDENCE. METER SET WAS SHUT OFF UPON ARRIVAL. THE FIRE DEPARTMENT BELIEVES THE FIRE STARTED INSIDE THE FRONT OF... |
GD-20250060_0 | GD-20250060 | Report GD-20250060 | AL | 2025 | GAS DISTRIBUTION | EXCAVATION DAMAGE
Extracted: severity_weak_label=moderate
Narrative: ON THE 18TH OF OCTOBER 2025 AT 3:44PM DEKALB CHEROKEE GAS (DC GAS) WAS NOTIFIED OF A GAS LEAK AT THE INTERSECTION OF DEKALB COUNTY ROAD 51 AND DEKALB COUNTY ROAD 212. CALLER STATED THAT A MILLING MA... |
GD-20250059_0 | GD-20250059 | Report GD-20250059 | FL | 2025 | GAS DISTRIBUTION | EXCAVATION DAMAGE
Extracted: severity_weak_label=moderate
Narrative: A THIRD-PARTY CONTRACTOR WAS INSTALLING ELECTRICAL CONDUIT FOR A NEW RESIDENCE. THE CONTRACTOR HAD LOCATED AND IDENTIFIED THE GAS MAIN, BUT FAILED TO DETERMINE THE CLEARANCE NECESSARY TO AVOID STRIKI... |
GD-20250058_0 | GD-20250058 | Report GD-20250058 | GA | 2025 | GAS DISTRIBUTION | EXCAVATION DAMAGE
Extracted: severity_weak_label=moderate
Narrative: A THIRD-PARTY PARTY EXCAVATOR (MEER ELECTRIC) STRUCK AND DAMAGED AN ATLANTA GAS LIGHT COMPANY (AGLC) 2-INCH PLASTIC GAS MAIN WHILE HORIZONTAL DIRECTIONALLY DRILLING TO INSTALL A NEW WATER SERVICE TO ... |
GD-20250057_0 | GD-20250057 | Report GD-20250057 | OH | 2025 | GAS DISTRIBUTION | OTHER OUTSIDE FORCE DAMAGE
Extracted: severity_weak_label=moderate
Narrative: 3RD PARTY VEHICLE OPERATOR RAN OFF ROADWAY AND STRUCK REGULATION & METERING STATION, CAUSING SIGNIFICANT DAMAGE TO THE BUILDING STRUCTURE, REGULATORS, METERS, FILTER AND OTHER EQUIPMENT. ES... |
GD-20250055_0 | GD-20250055 | Report GD-20250055 | NC | 2025 | GAS DISTRIBUTION | OTHER OUTSIDE FORCE DAMAGE
Extracted: severity_weak_label=severe
Narrative: AT APPROXIMATELY 11:20 AM 911 CALLED PNG CUSTOMER CONTACT CENTER TO REPORT THAT A VEHICLE HIT AND DAMAGED OUR ASSET. THE VEHICLE THAT HIT THE PNG DESIGN METER BENT THE 2” RISER AND BROKE OFF A... |
GD-20250054_0 | GD-20250054 | Report GD-20250054 | NJ | 2025 | GAS DISTRIBUTION | EXCAVATION DAMAGE
Extracted: severity_weak_label=moderate
Narrative: AT APPROXIMATELY 9:41AM SOUTH JERSEY GAS (SJG) DISPATCH RECEIVED A CALL ADVISING OF A STRUCK GAS FACILITY. SJG DISPATCHED A FIRST RESPONDER IMMEDIATELY. SJG FIRST RESPONDER ARRIVED AT 10:03AM. HE... |
GD-20250053_0 | GD-20250053 | Report GD-20250053 | TX | 2025 | GAS DISTRIBUTION | EXCAVATION DAMAGE
Extracted: severity_weak_label=minor
Narrative: ON JULY 29, 2025, AT APPROXIMATELY 8:00 A.M., ATMOS ENERGY RECEIVED NOTIFICATION THAT A THIRD-PARTY EXCAVATOR HAD DAMAGED A 24-INCH STEEL GAS MAIN. AN ATMOS ENERGY TECHNICIAN ARRIVED ON SITE AT 8:17 A.... |
GD-20250051_0 | GD-20250051 | Report GD-20250051 | MI | 2025 | GAS DISTRIBUTION | OTHER OUTSIDE FORCE DAMAGE
Extracted: severity_weak_label=moderate
Narrative: ON FRIDAY, JULY 25, 2025, AT APPROXIMATELY 17:45, CONSUMERS ENERGY GAS CONTROL RECEIVED MULTIPLE SCADA ALARMS INDICATING A POTENTIAL FAILURE AT DISTRIBUTION REGULATOR STATION 64-301, LOCATED... |
GD-20250051_1 | GD-20250051 | Report GD-20250051 | MI | 2025 | GAS DISTRIBUTION | OTHER OUTSIDE FORCE DAMAGE
Extracted: severity_weak_label=moderate
Narrative: UPON COMPLETION OF THE INVESTIGATION. THE INVESTIGATION CONCLUDED THAT THE REGULATOR STATION FIRE WAS CAUSED BY AN ELECTRICAL ARC FAULT ON NEARBY ELECTRIC UTILITY LINES SERVING THE ADJACENT ... |
GD-20250052_0 | GD-20250052 | Report GD-20250052 | IL | 2025 | GAS DISTRIBUTION | NATURAL FORCE DAMAGE
Extracted: severity_weak_label=moderate
Narrative: LIGHTNING STRUCK A UTILITY POLE CAUSING A HIGH-VOLTAGE POWER LINE TO FALL AND ARC THROUGH THE GROUND. THE ELECTRICAL ARC DAMAGED THE GAS MAIN RESULTING IN A RELEASE AND IGNITION. SUBSEQUENTLY, A... |
GD-20250050_0 | GD-20250050 | Report GD-20250050 | TX | 2025 | GAS DISTRIBUTION | OTHER OUTSIDE FORCE DAMAGE
Extracted: severity_weak_label=critical
Narrative: ON JULY 21, 2025, AT 3:56PM, CENTERPOINT ENERGY WAS NOTIFIED OF A HOUSEFIRE AT 1901 CHILTON DR., BAYTOWN, TX. WHEN THE RESPONDING TECHNICIAN ARRIVED ON SITE AT 4:20PM, IT WAS CONFIRMED THAT... |
GD-20250043_0 | GD-20250043 | Report GD-20250043 | TN | 2025 | GAS DISTRIBUTION | NATURAL FORCE DAMAGE
Extracted: severity_weak_label=moderate
Narrative: ON THE MORNING OF JULY 16TH, 2025, THERE WAS INCLEMENT WEATHER IN THE AREA. GAS CONTROL NOTIFIED LOCAL OPERATIONS OF A HIGH-PRESSURE ALARM AT K.P. STATION. LOCAL OPERATIONS WERE DISPATCHED TO THE ... |
GD-20250047_0 | GD-20250047 | Report GD-20250047 | NJ | 2025 | GAS DISTRIBUTION | OTHER INCIDENT CAUSE
Extracted: severity_weak_label=moderate
Narrative: ON MONDAY, JULY 14, 2025, PSE&G WAS NOTIFIED OF A HOUSE EXPLOSION AT 643 PARKVIEW AVENUE, NORTH PLAINFIELD THAT OCCURRED AT APPROXIMATELY 23:54 HRS. THE LOCAL FIRE DEPARTMENT WAS ABLE TO EXTINGUI... |
GD-20250046_0 | GD-20250046 | Report GD-20250046 | TX | 2025 | GAS DISTRIBUTION | EXCAVATION DAMAGE
Extracted: severity_weak_label=minor
Narrative: ON JULY 10, 2025, AT APPROXIMATELY 3:00 P.M., ATMOS ENERGY RECEIVED NOTIFICATION THAT A THIRD-PARTY EXCAVATOR HAD DAMAGED A 6-INCH POLYETHYLENE GAS MAIN. AN ATMOS ENERGY TECHNICIAN ARRIVED ON SITE AND ... |
GD-20250045_0 | GD-20250045 | Report GD-20250045 | UT | 2025 | GAS DISTRIBUTION | OTHER OUTSIDE FORCE DAMAGE
Extracted: severity_weak_label=severe
Narrative: ENBRIDGE GAS UTAH RESPONDED WHEN A VEHICLE HIT A1 1/4” RISER LOCATED APPROXIMATELY 45 FEET FROM THE STREET CAUSING A RELEASE OF GAS, FIRE, AND AN EVENTUAL EXPLOSION. THE RISER WAS FED BY A 6-I... |
GD-20250041_0 | GD-20250041 | Report GD-20250041 | OH | 2025 | GAS DISTRIBUTION | OTHER INCIDENT CAUSE
Extracted: severity_weak_label=critical
Narrative: NARRATIVE EXCEEDS CHARACTER LIMIT. COMPLETE NARRATIVE EMAILED TO USDOT PHMSA ACCIDENT INVESTIGATION DIVISION ON 4/10/26 |
GD-20250040_0 | GD-20250040 | Report GD-20250040 | IL | 2025 | GAS DISTRIBUTION | OTHER INCIDENT CAUSE
Extracted: severity_weak_label=critical
Narrative: PER NATIONAL TRANSPORTATION SAFETY BOARD ("NTSB") INVESTIGATION ID PLD25FR006, THE FOLLOWING INFORMATION IS PRELIMINARY AND SUBJECT TO CHANGE. ON JUNE 12, 2025, A NATURAL GAS-FUELED EXPLOSION ... |
GD-20250039_0 | GD-20250039 | Report GD-20250039 | IL | 2025 | GAS DISTRIBUTION | EXCAVATION DAMAGE
Extracted: severity_weak_label=moderate
Narrative: WHILE GRADING THE AREA, THE GRADER STRUCK THE GAS MAIN RELEASING GAS TO ATMOSPHERE. THE RELEASED GAS IGNITED, DAMAGING THE GRADER AND AN ADDITIONAL TWO PIECES OF CONSTRUCTION EQUIPMENT. THE FIRE SERV... |
GD-20250037_0 | GD-20250037 | Report GD-20250037 | TX | 2025 | GAS DISTRIBUTION | EXCAVATION DAMAGE
Extracted: severity_weak_label=minor
Narrative: ON JUNE 5, 2025, AT APPROXIMATELY 3:18 P.M., ATMOS ENERGY RECEIVED A CALL REPORTING A DAMAGE TO OUR FACILITIES AT 174 CYPRESS STREET, ABILENE, TEXAS. THE 10-INCH LOW PRESSURE MAIN WAS DENTED SEVERAL TI... |
GD-20250038_0 | GD-20250038 | Report GD-20250038 | TX | 2025 | GAS DISTRIBUTION | MATERIAL FAILURE OF PIPE OR WELD
Extracted: severity_weak_label=severe
Narrative: ON 5/31/2025, THE CPS ENERGY SYSTEM OPERATOR RECEIVED CALLS FROM THE SAN ANTONIO FIRE DEPARTMENT INDICATING A STRUCTURE FIRE. THE ADDRESS PROVIDED TO CPE ENERGY WAS 7902 LAUREL BEND. AT ... |
GD-20250038_1 | GD-20250038 | Report GD-20250038 | TX | 2025 | GAS DISTRIBUTION | MATERIAL FAILURE OF PIPE OR WELD
Extracted: severity_weak_label=severe
Narrative: A LEAK CREW, CONTINUED BAR HOLE TESTING AND PERFORMING OTHER ANALYSES OF CPS ENERGY EQUIPMENT AND FACILITIES THROUGHOUT THE NIGHT. ADDITIONAL RESOURCES WERE CALLED AS APPROPRIATE AND AS ... |
GD-20250035_0 | GD-20250035 | Report GD-20250035 | OH | 2025 | GAS DISTRIBUTION | EXCAVATION DAMAGE
Extracted: severity_weak_label=moderate
Narrative: AT APPROXIMATELY 10:40AM EDT ON MAY 7, 2025, AN ENBRIDGE GAS OHIO 4" INTERMEDIATE PRESSURE (IP) DISTRIBUTION MAINLINE (MAOP 80PSIG) WAS DAMAGED BY A 3RD PARTY CONTRACTOR. THE CONTRACTOR WAS INSTALLIN... |
GD-20250035_1 | GD-20250035 | Report GD-20250035 | OH | 2025 | GAS DISTRIBUTION | EXCAVATION DAMAGE
Extracted: severity_weak_label=moderate
Narrative: AND ALL RESIDENTS WERE EVACUATED. THE WOOSTER FIRE DEPARTMENT AND POLICE DEPARTMENT ARRIVED SHORTLY AFTER. NOTIFICATIONS OF THE INCIDENT WERE COMPLETED TO THE NATIONAL RESPONSE CENTER AND PUBLIC UTIL... |
GD-20250034_0 | GD-20250034 | Report GD-20250034 | TN | 2025 | GAS DISTRIBUTION | EXCAVATION DAMAGE
Extracted: severity_weak_label=minor
Narrative: A CONTRACTOR WAS INSTALLING A SEWER MAIN USING A DIRECTIONAL DRILLER. DURING THE PROCESS THE CONTRACTOR DRILLED INTO AN 8-INCH DISTRIBUTION MAIN. ORIGINALLY WHEN THIS INCIDENT OCCURRED THE PRICE ... |
GD-20250036_0 | GD-20250036 | Report GD-20250036 | SC | 2025 | GAS DISTRIBUTION | EXCAVATION DAMAGE
Extracted: severity_weak_label=minor
Narrative: A THIRD-PARTY CONTRACTOR CAME INTO CONTACT WITH A 2" PL GAS MAIN AT HARDEN ST. AND SLIGHS AVE. IN COLUMBIA, SC ON THE AFTERNOON OF SATURDAY, MAY 3, 2025. NO CUSTOMERS EXPERIENCED AN INTERRUPTION OF GAS... |
GD-20250030_0 | GD-20250030 | Report GD-20250030 | NC | 2025 | GAS DISTRIBUTION | OTHER OUTSIDE FORCE DAMAGE
Extracted: severity_weak_label=moderate
Narrative: A GAS REGULATOR STATION WAS STRUCK BY A DWI DRIVER AND CAUGHT FIRE AS A RESULT. THE DAMAGE RESULTED IN 50 CUSTOMER OUTAGES. |
GD-20250031_0 | GD-20250031 | Report GD-20250031 | MO | 2025 | GAS DISTRIBUTION | EXCAVATION DAMAGE
Extracted: severity_weak_label=severe
Narrative: A THIRD-PARTY EXCAVATOR WAS BACKFILLING WHEN THEY DAMAGED A 1-INCH NIPPLE ON A 10-INCH STEEL NATURAL GAS PIPELINE. ALTHOUGH THE COMPANY'S PROCEDURES STATE THAT OPERATION OF MECHANIZED EQUIPMENT SHALL C... |
End of preview. Expand in Data Studio