October 19, 2019 Nestle/ Gerber Products Company Preferred Electrical Component List
Gerber Fremont Preferred Electrical Component List 5-27-21.pdf
Preferred Equipment Specification Vendor and Component List Nestlé/Gerber Products Company 5/27/2021 Page 2 of 11 Table of Contents 1. 0 Hardware: Electrical Controls................................................................................................................ 3 2. 0 Programmable Logic Controllers (PLC) Components............................................................................ 5 3. 0 Hardware: Pumps, Valves..................................................................................................................... 6 4. 0 Software................................................................................................................................................ 6 5. 0 Server, PC, and Network Equipment..................................................................................................... 6 6. 0 Hardware: Instrumentation.................................................................................................................... 7 7. 0 Power Distribution................................................................................................................................. 8 8. 0 Sensors, Switches................................................................................................................................. 9 9. 0 Uninterruptible Power Supply (UPS)..................................................................................................... 9 10. 0 Safety.................................................................................................................................................. 9 11. 0 Raceways......................................................................................................................................... 10 12. 0 Motor Control Centers (MCC).......................................................................................................... 101
Gerber Fremont Preferred Electrical Component List 5-27-21.pdf
Preferred Equipment Specification Vendor and Component List Nestlé/Gerber Products Company 5/27/2021 Page 3 of 11 Document Description The following sections list the approved Vendors for each type of component. Written prior approval from owner is required to use components not included in this list. If indicating alternate equipment, contact Nestlé Designated Electrical Resource and confirm approval. 1. 0 Hardware: Electrical Controls Component Type Specific Manufacturer Specific Model Comments Cables Quick Disconnect IP69K rated for wet locations Fill connection to sensor with dielectric grease. Cabling TC-ER Rated Control Circuit Breakers Prefer Allen-Bradley Finger Safe Control Transformers Prefer Allen-Bradley Finger Safe Fuse Blocks Prefer Allen-Bradley Finger Safe Multi Pole Interlocked Blown Fuse Indicator Preferred Fuses Bussman Current Limiting (Low Peak) Junction Boxes All wired not passing through shall be terminated and labeled No top penetrations Local Motor Disconnects Hubbell/Mennekes preferred one N. O. Auxillary contact for feedback No top penetrations Molded Case Circuit Breakers 65K AIC Rated Network Ethernet Switch Prefer Allen-Bradley Stratix Unmanaged Ports
Gerber Fremont Preferred Electrical Component List 5-27-21.pdf
Preferred Equipment Specification Vendor and Component List Nestlé/Gerber Products Company 5/27/2021 Page 4 of 11 Panel Enclosures Hoffman/SCE 316L SS unless approved by E&A Rep. Sloped top in wet locations See E&A rep regarding labeling requirements Have a disconnecting means outside of main panel to create electrically safe work conditions inside while servicing Separation barrier between voltages <50v and >50v Lighting disconnect to keep PLC/HMI/Panel Lighting powered up while main locked out. VFD/Servo Drives require AC Unit Inside Lighting to be LED switched on by cabinet door being open No top penetrations Panel Interface Port Grace Preferred E&A rep. approval needed if installing in wet location Power Supplies Prefer Allen-Bradley Finger Safe Push Buttons, Panel and Stack Lights Prefer Allen-Bradley 800T 856T Finger Safe LED for all indicators Nonmetallic versions in wash-down areas Servo Controller Allen-Bradley Kinetix 6500 480vac Line 24vdc control Ethernet Servo Motor Allen-Bradley VFD Allen-Bradley PF 525 Top of frame Stack Lights Allen-Bradley/Banner Preferred 24vdc LED Banner recommended for wet locations Terminals Prefer Allen-Bradley Screw Type Finger Safe
Gerber Fremont Preferred Electrical Component List 5-27-21.pdf
Preferred Equipment Specification Vendor and Component List Nestlé/Gerber Products Company 5/27/2021 Page 5 of 11 Wires to enter Top side/left side and exit bottom/right side. Disconnect Switch Prefered Hubbell HBLDS3P HBLDS6P Lockable Disconnect Switch 2. 0 Programmable Logic Controllers (PLC) Components Component Type Specific Manufacturer Specific Model Comments HMI Terminal Allen-Bradley Panelview Plus 7 24V 10" or larger displays only Confirm panelview with E&A rep. Factory Talk User must be created with this login- ELECT and this password- 3391 Version 10 PLC Chassis Allen-Bradley Allow for 30% future expansion PLC Communications Allen-Bradley Need one Ethernet connection to plant network Need one Ethernet connection to local machine network Dual port processor can fulfill this Plant network IP addresses to be given by Gerber E&A rep. upon request PLC I/O Modules Allen-Bradley Fuse all discrete outputs that control field devices 24V Control PLC Power Supplies Allen-Bradley Size to allow for 30% future expansion PLC Processor Allen-Bradley Preferred Compact Logix 5069 Control Logix L72S, L73S Logix 5000 Platform Version 30 or 32 Confirm processor with E&A rep. Programming to follow Nestle Gerber standard (NEAT)
Gerber Fremont Preferred Electrical Component List 5-27-21.pdf
Preferred Equipment Specification Vendor and Component List Nestlé/Gerber Products Company 5/27/2021 Page 6 of 11 3. 0 Hardware: Pumps, Valves, Solenoids. Component Type Specific Manufacturer Specific Model Comments Solenoid SMC EX260-SEN1 24VDC Ethernet Module 4. 0 Software Any installation of a component that will require Gerber to install new software for support must be reviewed and approved by E&A rep before install. 5. 0 Server, PC, and Network Equipment Network cabling to be color coded to plant standard. Request through E&A rep. or plant IT Lead Component Type Specific Manufacturer Specific Model Comments Wonderware All servers and licenses are provided by Nestle Discuss with E&A Engineer for approval Use Archestr A MES Discuss with E&A Engineer for approval Historian Use Wonderware historian A copy of the program must be given to E&A rep. prior to vendor leaving facility after project commissioning completed. Ethenet I/O-Armor Block Allen Bradley 1732E-IB8M8SOER 1732E-OB8M8SR 24VDC Ethernet Armor Block Modules Daisy Chained Pwr and Comms Bar Code Scanner Cognex DM362X Dataman Barcode Reader. 24VDC/Ethernet. Should include Lens/Red Polarizer and Vision View Software installed on HMI
Gerber Fremont Preferred Electrical Component List 5-27-21.pdf
Preferred Equipment Specification Vendor and Component List Nestlé/Gerber Products Company 5/27/2021 Page 7 of 11 PC's/Thin Clients/Server Hardware/Network Hardware Discuss with E&A Engineer for approval Patch cables Patch Cables-Cont. Panduit Panduit Must have factory-provided end-connectors and adhere to the following color code. PLC VLAN-Green; SCADA VLAN-Blue Must use CAT 6 cabling, terminated to a patch panel port at the appropriate IDF. At end-user location, cable must be terminated at a wall-box with appropriate RJ-45 connector. 6. 0 Hardware: Instrumentation Component Type Specific Manufacturer Specific Model Comments Chart Recorders Yokogawa Paperless GX 20 24VDC Install on front of panel and cover with a window Ethernet Communications. Must have both MC and MT options enabled Conductivity Sensors Rosemount 56 Model with Toroidal IP69K Rated 24VDC Controller mounted in separate panel behind a window Hart & Ethernet Communications Cabling TC-ER Rated Flow Sensors Rosemount Coriolis Preferred IP69K Rated 24VDC Hart & Ethernet
Gerber Fremont Preferred Electrical Component List 5-27-21.pdf
Preferred Equipment Specification Vendor and Component List Nestlé/Gerber Products Company 5/27/2021 Page 8 of 11 Communications Cabling TC-ER Rated I2P Signal Converters 24VDC Level Sensors Rosemount-Pressure Vega- Pressure/Radar/Capacitance/Ultrasonic Rice Lakes-Weight Measure by pressure preferred IP69K Rated 24VDC Hart & Ethernet Communications Cabling TC-ER Rated Pressure Sensors Rosemount/IFM 2" Tri-Clover IP69K Rated 24VDC Hart & Ethernet Communications Cabling TC-ER Rated Rosemount in high vibration applications External zero and span buttons Standalone Controllers Honeywell UDC4500 24VDC Install on front of panel and cover with a window Ethernet Communications Temperature Sensors- RTD Burns 100 ohm plati num 385 curve IP69K Rated 24VDC Installed in thermowells Transmitter in cabinet (Not in head) Hart & Ethernet Communications Cabling TC-ER Rated Weight (scale) Rice Lake RL2200 Load Cells / 720i Indicators 24VDC Hart & Ethernet Communications Cabling TC-ER Rated 7. 0 Power Distribution Component Type Specific Manufacturer Specific Model Comments Substation Square D/Eaton Size for 30% future expansion Panelboards /Breaker Panel Square D i Line Size for 30% future expansion
Gerber Fremont Preferred Electrical Component List 5-27-21.pdf
Preferred Equipment Specification Vendor and Component List Nestlé/Gerber Products Company 5/27/2021 Page 9 of 11 8. 0 Sensors, Switches Component Type Specific Manufacturer Specific Model Comments Limit Switch es Cabled versions in wash-down areas Fill QD connections with dielectric grease Photoelectric /Laser Sensors 24V Cabled versions in wash-down areas Fill QD connections with dielectric grease Proximity Sensors 24V Cabled versions in wash-down areas Fill QD connections with dielectric grease Vision Sensors Cognex Preferred 24V Cabled versions in wash-down areas Fill QD connections with dielectric grease 9. 0 Uninterruptible Power Supply (UPS) Component Type Specific Manufacturer Specific Model Comments 10. 0 Safety Component Type Specific Manufacturer Specific Model Comments Safety Relays Allen-Bradley Safety PLd Category 3+ Safety Contactors Allen-Bradley Safety PLd Category 3+ Safety Guard Sensors Allen-Bradley RFID Non-Contact Models Only Safety PLd Category 3+ Safety Light Curtains Allen-Bradley Preferred/Banner Safety PLd Category 3+
Gerber Fremont Preferred Electrical Component List 5-27-21.pdf
Preferred Equipment Specification Vendor and Component List Nestlé/Gerber Products Company 5/27/2021 Page 10 of 11 Safety Gate Switches Allen-Bradley 442G Multifunctional Access Box Safety PLd Category 3+ E-stop, Request to enter (blue), and reset (white/clear) pushbuttons on switch required as well 11. 0 Raceways For medium/high hygiene locations where cable tray is required, please refer to Nestle Gerber installation standard. Component Type Specific Manufacturer Specific Model Comments Cable Tray Cablofil preferred In 316L SS Required in Medium/High hygiene locations No sharp edges after cuts made Maintain a continuous run of tray from panel to device Cables in tray to be zip tied every 1' Size for 30% future expansion Conduit Galvanized RMC for low hygiene locations Thin wall EMT only with E&A prior approval 12. 0 Motor Control Centers (MCC) Component Type Specific Manufacturer Specific Model Comments Motor Control Centers Allen-Bradley Centerline Intelli Center Size for 30% future expansion Components to have 65K AIC rating Finger Safe 480VAC-Line 24VDC-Control Allow for view of VFD status without opening
Gerber Fremont Preferred Electrical Component List 5-27-21.pdf
Preferred Equipment Specification Vendor and Component List Nestlé/Gerber Products Company 5/27/2021 Page 11 of 11 doors by having window or installing HIM on cover. END OF DOCUMENT
Gerber Fremont Preferred Electrical Component List 5-27-21.pdf
README.md exists but content is empty. Use the Edit dataset card button to edit it.