77d4ead2-62d2-4b84-9580-bffaa55c3e77
What classification do supply conductors fall under when overcurrent protection is provided as part of the industrial control panel?
[ "When overcurrent protection is provided as part of the industrial control panel, the supply conductors shall be considered as either feeders or taps as covered by 240.21." ]
[ [ "409.21(B)" ] ]
34f69761-679b-423b-a975-3d827b748a75
What requirements must a motor-compressor controller meet regarding the continuous-duty full-load current rating?
[ "A motor-compressor controller must have both a continuous-duty full-load current rating and a locked-rotor current rating that are not less than the name-plate rated-load current or branch-circuit selection current, whichever is greater." ]
[ [ "440.41(A)" ] ]
71dc70f1-609b-41ef-836b-61a85d1c7304
What are the restrictions on using lighting equipment identified for horticultural use for general illumination?
[ "Lighting equipment identified for horticultural use shall not be installed as lighting for general illumination unless such use is indicated in the manufacturer's instructions." ]
[ [ "410.176(A)" ] ]
9affdc93-fdd8-45dc-a2d9-6ad990d1fa5c
What is the purpose of a thermal protector in motor circuits?
[ "The purpose of a thermal protector in motor circuits is to protect each motor against dangerous heating due to motor overloads and failure to start." ]
[ [ "430.206(B)(1)" ] ]
d3d4a8d4-1274-4733-bbb3-a1bcfc3630d6
What wiring methods are recognized for connecting heating panels to branch-circuit and supply wiring?
[ "The answer to given question is not present in context" ]
[ [ "424.99(B)(2)" ] ]
cae1827a-7db2-433a-a399-07ff130c5c21
What requirements must single-pole separable connectors meet to be considered listed for ac/dc use?
[ "Single-pole separable connectors must be listed for ac/dc use and marked in a suitable manner to identify the system to which they are intended to be connected." ]
[ [ "406.13(C)" ] ]
69d3dbbd-75b7-49bd-9f0a-1ad07e5375ce
What are the provisions that apply to boilers operating at 600 volts, nominal, or less?
[ "The provisions in Part VIII and Part VII of this article apply to boilers for operation at 600 volts, nominal, or less, in which heat is generated by the passage of current between electrodes through the liquid being heated." ]
[ [ "424.80", "425.80" ] ]
5676e014-e5d2-4ffe-b0aa-d97962adcf36
What guidelines should be followed to determine current ratings for general motor applications?
[ "Current ratings for general motor applications shall be determined based on 430.6(A)(1) and (A)(2)." ]
[ [ "430.6(A)" ] ]
05256cca-66f5-47fc-bf13-48fd0140f510
What are the conditions under which motors can be permitted on a branch circuit protected at not over 20 amperes?
[ "Motors can be permitted on a branch circuit protected at not over 20 amperes if the following conditions are met: Each motor's full-load rating does not exceed 6 amperes, the rating of the branch-circuit short-circuit and ground-fault protective device marked on any of the motor controllers is not exceeded, and individual overload protection conforms to 430.32." ]
[ [ "430.53(A)" ] ]
b1fd1d8b-5481-4a70-a970-187d79c8244d
What are the requirements for using liquidtight flexible conduit to enclose leads to a motor?
[ "Liquidtight flexible nonmetallic conduit and rigid nonmetallic conduit shall be permitted to enclose the leads to the motor if the leads are stranded and the required equipment grounding conductor is connected to both the motor and to the box." ]
[ [ "430.245(A)", "430.245(B)" ] ]
f7fc26b7-63fb-445c-a880-e367cc972411
What are the requirements for output motor conductor protection in relation to the ampacity of conductors?
[ "The requirements for output motor conductor protection state that the conductors between the power conversion equipment and the motor must have an ampacity equal to or larger than 125 percent of the motor full-load current as determined by 430.6(A) or (B). If the power conversion equipment is marked as 'Suitable for Output Motor Conductor Protection,' the conductor must have an ampacity equal to or greater than the larger of 125 percent of the motor full-load current or the ampacity of the minimum conductor size marked on the power conversion equipment." ]
[ [ "430.122(B)" ] ]
cb6f445a-a016-4534-b7a2-d6105cb591cb
What is the role of the factory-installed attachment plug in cord-and-plug-connected equipment rated 20 amperes or less?
[ "The factory-installed attachment plug in cord-and-plug-connected equipment rated 20 amperes or less and 150 volts or less to ground shall be permitted to be the disconnecting means." ]
[ [ "426.50(B)" ] ]
30736a23-2559-45f1-9875-b16687e08a6e
What ensures weatherproofing for 15 & 20 amp outlets in wet areas?
[ "Weatherproofing for 15 and 20 amp outlets in wet areas is ensured by requiring that these receptacles have an enclosure that is weatherproof, regardless of whether the attachment plug cap is inserted. Additionally, the outlet box hood must be listed and identified as extra-duty, and other listed products providing weatherproof protection do not need to be identified as extra duty." ]
[ [ "406.9(B)(1)" ] ]
bfa4223d-1e86-4200-9766-2bcb0b20069f
What's the min size for neutral conductors with ground-fault currents per generator ratings?
[ "Neutral conductors of dc generators that must carry ground-fault currents shall not be smaller than the minimum required size of the largest conductor." ]
[ [ "445.13(A)" ] ]
b5d46d17-a8ab-46d9-b361-49d22ad0768f
What's the role of capacitors in circuits, aside from surge types?
[ "The answer to given question is not present in context" ]
[ [ "460.1" ] ]
0b8e66a0-fd55-4f99-b5fd-a1422c3e5339
How do separate reactors boost circuit performance?
[ "The answer to given question is not present in context" ]
[ [ "470.1", "460.1" ] ]
bb224db9-638a-4f76-8a31-3a872189d231
What should be marked on electrode boilers for safety?
[ "Electrode-type boilers shall be marked to show the manufacturer's name, the rating in volts, amperes, and kilowatts, the electrical supply required specifying frequency, number of phases, and number of wires, the marking 'Electrode-Type Process Heating Boiler,' and a warning marking, 'All Power Supplies Shall Be Disconnected Before Servicing, Including Servicing the Pressure Vessel.' Additionally, a field-applied warning marking or label shall comply with 110.21 (B)." ]
[ [ "425.86" ] ]
1700911d-6c1e-4c62-95a3-1c2c4b0c8e04
What factors add up for motor and non-motor ampacity?
[ "The factors that add up for motor and non-motor ampacity include: 125 percent of the full-load current rating of the highest rated motor, the sum of the full-load current ratings of all the other motors in the group, 100 percent of the noncontinuous non-motor load, and 125 percent of the continuous non-motor load." ]
[ [ "430.24" ] ]
c27b600f-a6ed-4d74-8282-80d6778f2a2a
What are the limits for temp-controlled switches with ungrounded conductors?
[ "Temperature controlled switching devices that do not have an 'off' position shall not be required to open all ungrounded conductors and shall not be permitted to serve as the disconnecting means." ]
[ [ "426.51(B)" ] ]
0cb9f87a-17c8-4055-9a0a-26eae84a9963
What protects motors from overheating?
[ "Overload devices are intended to protect motors from overheating due to excessive heating caused by motor overloads and failure to start." ]
[ [ "430.31" ] ]
ac29155b-414e-4335-863e-139719d7e703
What exempts conductors for a single motor from protective devices?
[ "Conductors supplying a single motor are exempt from having an individual branch-circuit short-circuit and ground-fault protective device if they comply with 430.53(D)(1) or (D)(2)." ]
[ [ "430.53(D)" ] ]
7ca26d1e-a2df-4d66-a415-e857e34c1299
What affects overload device rating with motor service factor & temp rise?
[ "The overload device rating is affected by the motor service factor and temperature rise. Specifically, motors with a marked service factor of 1.15 or greater or a marked temperature rise of 40°C or less should have an overload device rated at no more than 125% of the motor nameplate full-load current rating. All other motors should have an overload device rated at no more than 115%." ]
[ [ "430.32(A)(1)" ] ]
169979ca-a33c-427b-b86d-e75f300fa53d
What are the surface requirements for heating panel installation under flooring?
[ "Heating panels or panel sets installed under floor covering must be placed on surfaces that are smooth and flat, in accordance with the manufacturer's instructions, and must comply with 424.99(B)(1) through (B)(6)." ]
[ [ "424.99(B)" ] ]
49952b37-d4a1-48ed-80d4-38bc10eaf27b
What affects ampacity of 2000V cables in different temps?
[ "The ampacity of 2000V cables is affected by ambient temperatures other than 30°C (86°F), which require the application of temperature correction factors from Table 400.51(A)(2). Additionally, if the cable is not completely unwound from the cord reel, the ampacity correction factor based on the number of layers remaining wound on the reel must be applied as shown in Table 400.51(A)(3)." ]
[ [ "400.51(A)", "400.50" ] ]
d7eb4491-13c5-46d1-944a-a70a29168b83
What does a protective component do for conductors in wiring?
[ "A protective component, such as a bushing, is used to protect conductors from the edges of openings having sharp edges. It ensures that the conductors are safeguarded from potential damage caused by these sharp edges." ]
[ [ "445.16", "430.13" ] ]
63c6f1d1-d437-42da-9c1c-a1fb38c30088
What specs for the rear connection of a range ensure accessibility and compliance?
[ "For cord-and-plug-connected household electric ranges, the rear connection must have an attachment plug and receptacle connection that is accessible from the front by removal of a drawer. This ensures accessibility and compliance." ]
[ [ "422.33(B)", "422.33(A)" ] ]
b293198c-5342-43ef-8e98-d9c7176373fe
What's the meaning of the orange triangle on receptacles for isolated grounding?
[ "The orange triangle on receptacles indicates that they incorporate an isolated equipment grounding conductor connection intended for the reduction of electromagnetic interference, as permitted in 250.146(D)." ]
[ [ "406.3(E)", "406.3(E)(1)" ] ]
4eca2e37-21f9-4e7c-b19f-f4755cde8c04
What's the role of nailing strips in parallel heating panel installs with joists?
[ "The answer to given question is not present in context" ]
[ [ "424.93(B)(1)", "424.93(B)(2)" ] ]
f588cd1b-061c-406f-bdc8-be8337f1b531
What factors affect ampacity for portable feeders over 2000V, especially temp changes and cable stacking?
[ "The factors that affect ampacity for portable feeders over 2000V include ambient temperature and the number of layers of cable wound on a reel. For ambient temperatures other than 30°C (86°F), temperature correction factors from Table 400.51(A)(2) must be applied to the ampacity. Additionally, if the cable is not completely unwound from the cord reel, the ampacity correction factor based on the number of layers remaining wound on the reel, as shown in Table 400.51(A)(3), should be applied." ]
[ [ "400.51(A)", "400.50" ] ]
240caa60-d06b-4c60-a7ac-5965658d5e5c
What are the load subdivision rules for non-ASME boilers with >48A resistance heaters?
[ "For non-ASME boilers with resistance-type heating elements rated more than 48 amperes, the heating elements must be subdivided into loads not exceeding 48 amperes. If a subdivided load is less than 48 amperes, the rating of the overcurrent protective device must comply with 424.4(B)." ]
[ [ "424.72(B)", "425.72(B)" ] ]
7b1bb02c-5652-4dc4-8d19-0b20b5dfcc34
How does the outer finish help distinguish conductors in insulated cords, especially with color coding?
[ "The outer finish on insulated cords is permitted to provide the desired color, which helps distinguish the conductors, especially when the insulation on the individual conductors is integral with the jacket." ]
[ [ "400.22(C)", "400.22(D)" ] ]
c8dbbdde-dd81-406c-b8cf-945d97e7d1bd
What markings are needed for a luminaire with supply wire over 60°C?
[ "A luminaire requiring supply wire rated higher than 60°C (140°F) shall be marked with the minimum supply wire temperature rating on the luminaire and shipping carton or equivalent." ]
[ [ "410.80(A)" ] ]
b2352591-7629-4370-a872-212899ea245c
How do reactors and capacitors improve electrical circuits?
[ "The answer to given question is not present in context" ]
[ [ "470.1", "460.1" ] ]
f3212f95-dfde-43dc-bc3a-c7a00bfa5f7a
What locking feature do temp-controlled switches need to cut off ungrounded conductors when off?
[ "Temperature-controlled switching devices need to be capable of being locked in the open position to serve as the disconnecting means when cutting off ungrounded conductors in the 'off' position." ]
[ [ "426.51(A)", "427.56(A)" ] ]
806fc667-197b-4eec-9201-1ccf107768ec
What safety measures are needed for hermetic refrigerant motor-compressors?
[ "Safety measures for hermetic refrigerant motor-compressors include devices intended to protect the branch-circuit conductors, control apparatus, and motors against overcurrent due to short circuits and ground faults. These measures are in addition to or amendatory of the overcurrent protection requirements found elsewhere in the Code." ]
[ [ "440.1", "440.21" ] ]
d34bff49-632d-4d3f-9421-c4083a590a46
What are the requirements for installing receptacles with arc-fault and ground-fault protection?
[ "The requirements for installing receptacles with arc-fault and ground-fault protection include that arc-fault circuit-interrupter type and ground-fault circuit-interrupter type receptacles must be installed in a readily accessible location. Additionally, ground-fault circuit-interrupter protection must be provided where replacements are made at receptacle outlets that are required to be so protected elsewhere in the Code. Ground-fault circuit interrupters must be listed, and if the outlet box size does not permit the installation of a GFCI receptacle, a new receptacle of the existing type may be used, provided it is marked 'GFCI Protected' and 'No Equipment Ground.'" ]
[ [ "406.4(D)", "406.4(D)(3)" ] ]
947d4b85-eb32-47d8-b90a-d46c5f1f6096
What's the min conductor size for motors with a set overload trip?
[ "Conductors supplying motors shall be sized not less than the current trip setting of the motor overload protective device(s)." ]
[ [ "430.205(A)" ] ]
0ed45983-f886-4e6f-adf0-ff53d64d4769
What rules govern ampacity for conductors over 1000V with safety in mind?
[ "The rules governing ampacity for conductors supplying equipment rated over 1000 volts are specified in accordance with 315.60 or 430.205(A) and (B)." ]
[ [ "430.205" ] ]
ff6185a3-5abb-4407-899b-68908da9fe64
What safety labels are needed for a switchboard in fault mode?
[ "A switchboard in fault mode shall be legibly and permanently field marked with the following safety label: CAUTION: DC SYSTEM OPERATING - _____ VOLTS BETWEEN CONDUCTORS AND MAY OPERATE - _____ VOLTS TO GROUND FOR INDEFINITE PERIODS UNDER FAULT CONDITIONS." ]
[ [ "408.3(F)(5)" ] ]
ef96f527-9c45-47b2-8a42-e7e504c93f38
What are the safety requirements for water heater temp limits?
[ "All storage or instantaneous-type water heaters must be equipped with a temperature-limiting means in addition to its control thermostat to disconnect all ungrounded conductors. This means must be installed to sense maximum water temperature and can be either a trip-free, manually reset type or a type having a replacement element. Exceptions include storage water heaters suitable for use with a supply water temperature of 82°C (180°F) or above and a capacity of 60 kW or above, and instantaneous-type water heaters suitable for such use with a capacity of 4 L (1 gal) or less." ]
[ [ "422.47" ] ]
c13fdae8-2c50-44bd-ab8e-23f5fba92de3
How does insulation improve safety and performance of electrical cords in different environments?
[ "The answer to given question is not present in context" ]
[ [ "400.22(D)" ] ]
7da3d53a-4187-49fb-9004-64fade22622d
What are the limits on horticultural lights for general use?
[ "The answer to given question is not present in context" ]
[ [ "410.176(A)" ] ]
4c9fa0dc-8f25-4fdb-8b8f-0e1a6737cd88
What's the max rating for a branch-circuit protective device relative to the equipment's marked rating?
[ "The maximum rating for a branch-circuit protective device shall not exceed the rating marked on the equipment." ]
[ [ "430.54" ] ]
b065b686-61e3-4d74-83a3-f345e17669c7
What calls for weather-resistant boxes when replacing outlets?
[ "Weather-resistant receptacles shall be provided where replacements are made at receptacle outlets that are required to be so protected elsewhere in this Code." ]
[ [ "406.4(D)(6)" ] ]
9a7ad7ec-cca7-4a9a-96f7-07ec0c6843bc
What safety steps for energized parts if draw-out gear needs door access?
[ "Energized bare parts mounted on doors shall be guarded when the door must be opened for maintenance of equipment or removal of draw-out equipment." ]
[ [ "495.33" ] ]
ed9dda44-b0ba-418c-acb4-fa9032323a88
What are the thermal protection criteria for recessed high-intensity luminaires in cavities?
[ "Recessed high-intensity luminaires designed to be installed in wall or ceiling cavities shall have thermal protection and be identified as thermally protected." ]
[ [ "410.130(F)(1)" ] ]
1b440036-252a-4428-8111-67b720e475d0
How do knife switch blades stay open when inverted?
[ "Single-throw knife switches approved for use in the inverted position shall be provided with an integral mechanical means that ensures that the blades remain in the open position when so set." ]
[ [ "404.6(A)" ] ]
22dae3e1-10ff-427c-b371-48a1007dd309
What are the voltage requirements for a motor controller in a grounded circuit?
[ "In a grounded circuit, a motor controller with a slash rating (e.g., 120/240 volts or 480Y/277 volts) shall only be applied if the nominal voltage to ground from any conductor does not exceed the lower of the two values of the motor controller's voltage rating, and the nominal voltage between any two conductors does not exceed the higher value of the motor controller's voltage rating." ]
[ [ "430.83(E)" ] ]
35ecefba-5aec-4d36-ba88-8b3077d8ecd1
How do overcurrent protection specs differ for 3-wire vs. 2-wire dc generators, especially for armature leads?
[ "For 3-wire dc generators, overcurrent protection devices must be installed in each armature lead and are connected to actuate by the entire current from the armature. These devices can be a double-pole, double-coil circuit breaker or a 4-pole circuit breaker. In contrast, for 2-wire dc generators, overcurrent protection is permitted in only one conductor, and the overcurrent device must be actuated by the entire current generated, excluding the current in the shunt field, without opening the shunt field." ]
[ [ "445.12(E)", "445.12(B)" ] ]
3d86b245-93b6-4335-86bc-b57d3e0c08e6
What risks come from loose horticultural lighting?
[ "The answer to given question is not present in context" ]
[ [ "410.186" ] ]