all_as_fire_dataset / 500_pair_ds_as1851.json
juanmackie's picture
Update 500_pair_ds_as1851.json
60d57dc verified
raw
history blame contribute delete
No virus
34 kB
[
{
"instruction": "What is the objective of AS 1851-2012?",
"output": "The objective of AS 1851-2012 is to maintain the reliability of fire protection systems and equipment such that they continue to meet the requirements of the approved design and are likely to do so until the next scheduled activity."
},
{
"instruction": "What is the scope of AS 1851-2012?",
"output": "This Standard sets out requirements for the routine servicing (inspection, testing, preventive maintenance and survey) of fire protection systems and equipment."
},
{
"instruction": "What does the term 'approved design' refer to in AS 1851-2012?",
"output": "The design of fire protection systems and equipment approved by the authority having jurisdiction at the time of installation or subsequent modification."
},
{
"instruction": "What is the difference between a critical defect, a non-critical defect and a non-conformance in AS 1851-2012?",
"output": "A critical defect renders a system inoperative, a non-critical defect is a system impairment or faulty component not likely to critically affect the operation of the system, and a non-conformance is a missing or incorrect feature that does not affect the system operation but is required to facilitate ongoing routine service."
},
{
"instruction": "What are the three main stages of the routine service process as described in AS 1851-2012?",
"output": "The three main stages of the routine service process are System design, installation and commissioning, Routine service, and Regulation and application of this Standard."
},
{
"instruction": "What is the purpose of baseline data in AS 1851-2012?",
"output": "Baseline data is necessary to establish the performance benchmark of the fire protection system or equipment."
},
{
"instruction": "What is the difference between inspection and survey in AS 1851-2012?",
"output": "Inspection is a visual examination of the components of fire protection systems or equipment to establish correct settings, physical condition or fitness for purpose. Survey is a visual inspection, typically conducted from floor level, to identify if the fire protection system or equipment has been inappropriately altered, damaged or compromised by changes in the occupancy, environment or building."
},
{
"instruction": "What are the frequencies of routine service activities for fire sprinkler systems in AS 1851-2012?",
"output": "The frequencies of routine service activities for fire sprinkler systems in AS 1851-2012 are monthly, six-monthly, yearly, five-yearly, ten-yearly, twenty-five yearly and thirty yearly."
},
{
"instruction": "What are the major changes made to AS 1851-2005 in this edition?",
"output": "The major changes made to AS 1851-2005 in this edition are: title changed to overcome reported ambiguity but still reflect the concept of inspection, test and preventive maintenance, restructured documentation requirements into service records and reporting to assist regulatory use, defined the relationship between initial installation, routine service and annual regulatory compliance, critically appraised and refined the routine service technical requirements in light of field experience and studies, facilitating the implementation of the Standard by the responsible entity and service provider, a thorough overhaul of the general requirements of Section 1, tables in Sections 2 to 14 changed from type based to frequency based, clarified requirements for interface testing, clarified role of commissioning and baseline data as part of the approved design, deletion of specific competency qualifications, distinguished between critical defects, non-critical defects and non-conformances, extensively revised records, removed ambiguity relating to current design Standards, Sections 6 to 10 have been combined in a new Section 6, routine service requirements for special hazard systems, a new Section 5 has been included, Sections 11, 12 and 13 have been combined in a new Section 7, and several new appendices."
},
{
"instruction": "What is the purpose of a yearly condition report in AS 1851-2012?",
"output": "A yearly condition report is a report prepared annually for the responsible entity, which summarizes the routine service activities, records operational status, notes defects and non-conformances and confirms that the installed fire protection systems and equipment generally accord with the approved design."
},
{
"instruction": "What are the requirements for fire pumpsets in AS 1851-2012?",
"output": "Fire pumpsets shall be subjected to routine service in accordance with Section 3 of this Standard."
},
{
"instruction": "What is the difference between fire detection and alarm systems, special hazards systems and smoke hazard management systems in AS 1851-2012?",
"output": "Fire detection and alarm systems detect fires and alert occupants. Special hazards systems are designed to suppress fires in specific areas with hazardous materials. Smoke hazard management systems are designed to control smoke spread in buildings."
},
{
"instruction": "What are the requirements for smoke alarms and heat alarms in AS 1851-2012?",
"output": "Smoke alarms and heat alarms shall be inspected and tested on a six-monthly and yearly basis in accordance with Clause 6.4.2 of this Standard."
},
{
"instruction": "What are the requirements for emergency warning systems in AS 1851-2012?",
"output": "Emergency warning systems shall be inspected and tested on a monthly, six-monthly and yearly basis in accordance with Clause 6.4.3 of this Standard."
},
{
"instruction": "What are the requirements for emergency intercom systems in AS 1851-2012?",
"output": "Emergency intercom systems shall be inspected and tested on a yearly basis in accordance with Clause 6.4.4 of this Standard."
},
{
"instruction": "What are the requirements for special hazard systems in AS 1851-2012?",
"output": "Special hazard systems, including gaseous, aerosol and open nozzle water mist special hazard fire suppression systems, shall be subjected to routine service at the intervals specified in Clause 7.4."
},
{
"instruction": "What are the requirements for delivery lay flat fire hose in AS 1851-2012?",
"output": "Delivery lay flat fire hose shall be serviced yearly, after usage and when defects are suspected."
},
{
"instruction": "What are the requirements for fire hose reels in AS 1851-2012?",
"output": "Fire hose reels shall be serviced six-monthly and yearly."
},
{
"instruction": "What are the requirements for portable and wheeled fire extinguishers in AS 1851-2012?",
"output": "Portable and wheeled fire extinguishers shall be serviced six-monthly, yearly and five-yearly."
},
{
"instruction": "What are the requirements for fire blankets in AS 1851-2012?",
"output": "Fire blankets shall be serviced at intervals not exceeding 6 months and when defects are suspected."
},
{
"instruction": "What are the requirements for passive fire and smoke systems in AS 1851-2012?",
"output": "Passive fire and smoke systems shall be inspected and tested on a yearly basis except for fire doors and smoke doors, which shall be inspected and tested on a six-monthly basis and sliding fire doors which shall be inspected and tested on a three-monthly basis."
},
{
"instruction": "What are the requirements for fire and smoke control features of mechanical services in AS 1851-2012?",
"output": "The fire and smoke control features of mechanical services shall be subjected to inspection, test and maintenance in accordance with Section 13 of this Standard."
},
{
"instruction": "What are the requirements for emergency planning in facilities in AS 1851-2012?",
"output": "The emergency plan and associated elements shall be inspected and tested at the specified periodic intervals and maintained to the requirements specified in Section 14 of this Standard."
},
{
"instruction": "How often should a fire hydrant system be inspected?",
"output": "Fire hydrant systems should be inspected monthly (pump-related inspection and test items only), six-monthly, yearly, and five-yearly."
},
{
"instruction": "What are the requirements for water storage tanks in AS 1851-2012?",
"output": "Water storage tanks for fire protection systems shall be subjected to routine service in accordance with Section 5 of this Standard."
},
{
"instruction": "What are the requirements for a fire-resistant doorset in AS 1851-2012?",
"output": "Fire-resistant doorsets shall be inspected and subjected to a routine service test and survey on a six-monthly basis in accordance with Clause 12.4.3.1."
},
{
"instruction": "How often should fire-resistant doorsets be inspected and tested?",
"output": "Hinged and pivoted fire-resistant doorsets should be inspected and tested six-monthly, except for those serving as entry doors to private residential apartments, which may be extended to a yearly service schedule. Horizontal sliding doors should be inspected and tested three-monthly and six-monthly."
},
{
"instruction": "What are the requirements for fire shutters in AS 1851-2012?",
"output": "Fire shutters shall be inspected and subjected to a routine service test and survey on a yearly basis in accordance with Clause 12.4.5."
},
{
"instruction": "How often should fire shutters be inspected and tested?",
"output": "Fire shutters should be inspected and tested yearly."
},
{
"instruction": "What are the requirements for fire-rated glazing in AS 1851-2012?",
"output": "Fire-rated glazing shall be inspected and subjected to a routine service, test and survey on a yearly basis in accordance with Clause 12.4.6."
},
{
"instruction": "How often should fire-rated glazing be inspected and tested?",
"output": "Fire-rated glazing should be inspected and tested yearly."
},
{
"instruction": "What are the requirements for fire-protected air ducts in AS 1851-2012?",
"output": "Fire-protected air ducts and dampers shall be inspected and subjected to a routine service, test and survey on a yearly basis in accordance with Clause 12.4.7."
},
{
"instruction": "How often should fire-protected air ducts be inspected and tested?",
"output": "Fire-protected air ducts should be inspected and tested yearly. Fire dampers, as part of the smoke management system, are covered in Section 13."
},
{
"instruction": "What are the requirements for fire and smoke curtains in AS 1851-2012?",
"output": "Fire curtains and smoke curtains shall be inspected and subjected to a routine service on a six-monthly and yearly basis in accordance with Clauses 13.4.1.11 and 13.4.1.12."
},
{
"instruction": "How often should fire and smoke curtains be inspected and tested?",
"output": "Fire curtains and smoke curtains should be inspected and tested six-monthly and yearly."
},
{
"instruction": "What are the requirements for motorized relief openings, windows and shutters in AS 1851-2012?",
"output": "Motorized relief openings, windows and shutters shall be inspected and subjected to a routine service on a six-monthly and yearly basis in accordance with Clauses 13.4.1.13 and 13.4.1.14."
},
{
"instruction": "How often should motorized relief openings, windows and shutters be inspected and tested?",
"output": "Motorized relief openings, windows and shutters should be inspected and tested six-monthly and yearly."
},
{
"instruction": "What are the requirements for electric heaters in AS 1851-2012?",
"output": "Duct or unit-mounted electric heaters shall be inspected and subjected to a routine service on a yearly basis in accordance with Clause 13.4.1.15."
},
{
"instruction": "How often should electric heaters be inspected and tested?",
"output": "Electric heaters should be inspected and tested yearly."
},
{
"instruction": "What are the requirements for kitchen exhaust systems in AS 1851-2012?",
"output": "Kitchen exhaust systems shall be inspected and subjected to a routine service on a monthly and yearly basis in accordance with Clauses 13.4.1.16 and 13.4.1.17."
},
{
"instruction": "How often should kitchen exhaust systems be inspected and tested?",
"output": "Kitchen exhaust systems should be inspected and tested monthly and yearly."
},
{
"instruction": "What are the requirements for outdoor intakes in AS 1851-2012?",
"output": "Outdoor intakes shall be inspected and subjected to a routine service on a monthly and yearly basis in accordance with Clauses 13.4.1.18 and 13.4.1.19."
},
{
"instruction": "How often should outdoor intakes be inspected and tested?",
"output": "Outdoor intakes should be inspected and tested monthly and yearly."
},
{
"instruction": "What are the requirements for variable frequency inverters (VFIs) in AS 1851-2012?",
"output": "Variable frequency inverters shall be inspected and subjected to a routine service on a three-monthly, six-monthly and yearly basis in accordance with Clauses 13.4.1.20, 13.4.1.21 and 13.4.1.22."
},
{
"instruction": "How often should variable frequency inverters be inspected and tested?",
"output": "Variable frequency inverters should be inspected and tested three-monthly, six-monthly and yearly."
},
{
"instruction": "What are the requirements for pneumatic compressor/receiver stations in AS 1851-2012?",
"output": "Pneumatic compressor/receiver stations shall be inspected and subjected to a routine service on a three-monthly and yearly basis in accordance with Clauses 13.4.1.23 and 13.4.1.24."
},
{
"instruction": "How often should pneumatic compressor/receiver stations be inspected and tested?",
"output": "Pneumatic compressor/receiver stations should be inspected and tested three-monthly and yearly."
},
{
"instruction": "What are the requirements for motor control centres in AS 1851-2012?",
"output": "Motor control centres shall be inspected and subjected to a routine service on a yearly basis in accordance with Clause 13.4.1.25."
},
{
"instruction": "How often should motor control centres be inspected and tested?",
"output": "Motor control centres should be inspected and tested yearly."
},
{
"instruction": "What are the requirements for power supplies—main switchboards (low voltage) in AS 1851-2012?",
"output": "Power supplies, main switchboards (low voltage) shall be inspected and subjected to a routine service on a yearly basis in accordance with Clause 13.4.1.26."
},
{
"instruction": "How often should power supplies—main switchboards (low voltage) be inspected and tested?",
"output": "Power supplies, main switchboards (low voltage) should be inspected and tested yearly."
},
{
"instruction": "What are the requirements for fire fan control panels (FFCP) and fire indicator panels (FIP) in AS 1851-2012?",
"output": "The fire fan control panel (FFCP) and fire indicator panel (FIP) shall be subjected to routine service in accordance with Section 6 of this Standard."
},
{
"instruction": "How often should fire fan control panels (FFCP) and fire indicator panels (FIP) be inspected and tested?",
"output": "Fire fan control panels (FFCP) and fire indicator panels (FIP) should be inspected and tested monthly, six-monthly, yearly, and five-yearly."
},
{
"instruction": "What are the requirements for fire-isolated exit pressurization systems in AS 1851-2012?",
"output": "Fire-isolated exit pressurization systems shall be tested on a three-monthly and yearly basis in accordance with Clauses 13.4.2.2 and 13.4.2.3."
},
{
"instruction": "How often should fire-isolated exit pressurization systems be inspected and tested?",
"output": "Fire-isolated exit pressurization systems should be inspected and tested three-monthly and yearly."
},
{
"instruction": "What are the requirements for system changeover under fire condition in AS 1851-2012?",
"output": "System changeover under fire condition shall be tested on a three-monthly and yearly basis in accordance with Clauses 13.4.2.4 and 13.4.2.5."
},
{
"instruction": "How often should system changeover under fire condition be inspected and tested?",
"output": "System changeover under fire condition should be inspected and tested three-monthly and yearly."
},
{
"instruction": "What are the requirements for smoke exhaust systems in AS 1851-2012?",
"output": "Smoke exhaust systems shall be tested on a three-monthly and yearly basis in accordance with Clauses 13.4.2.6 and 13.4.2.7."
},
{
"instruction": "How often should smoke exhaust systems be inspected and tested?",
"output": "Smoke exhaust systems should be inspected and tested three-monthly and yearly."
},
{
"instruction": "What are the requirements for system shutdown in AS 1851-2012?",
"output": "Systems shutdown shall be tested on a yearly basis in accordance with Clause 13.4.2.8."
},
{
"instruction": "How often should system shutdown be inspected and tested?",
"output": "System shutdown should be inspected and tested yearly."
},
{
"instruction": "What are the requirements for smoke dampers in AS 1851-2012?",
"output": "Smoke dampers shall be tested on a yearly basis in accordance with Clause 13.4.2.9."
},
{
"instruction": "How often should smoke dampers be inspected and tested?",
"output": "Smoke dampers should be inspected and tested yearly."
},
{
"instruction": "What are the requirements for active fire and smoke control systems in AS 1851-2012?",
"output": "Active fire and smoke control systems shall have a design and installation survey carried out on a yearly and five-yearly basis in accordance with Clause 13.4.3.2."
},
{
"instruction": "How often should active fire and smoke control systems be inspected and surveyed?",
"output": "Active fire and smoke control systems should be inspected and surveyed yearly and five-yearly."
},
{
"instruction": "What are the requirements for motorized relief openings (windows and shutters) in AS 1851-2012?",
"output": "Motorized relief openings (windows and shutters) shall have a design and installation survey carried out on a yearly basis in accordance with Clause 13.4.3.3."
},
{
"instruction": "How often should motorized relief openings (windows and shutters) be inspected and surveyed?",
"output": "Motorized relief openings (windows and shutters) should be inspected and surveyed yearly."
},
{
"instruction": "What are the requirements for smoke reservoirs in AS 1851-2012?",
"output": "Smoke reservoirs shall have a design and installation survey carried out on a yearly basis in accordance with Clause 13.4.3.4."
},
{
"instruction": "How often should smoke reservoirs be inspected and surveyed?",
"output": "Smoke reservoirs should be inspected and surveyed yearly."
},
{
"instruction": "What is the purpose of the Emergency Planning Committee (EPC) in AS 1851-2012?",
"output": "The Emergency Planning Committee (EPC) is responsible for developing and maintaining the emergency plan for the facility."
},
{
"instruction": "What is the purpose of the Emergency Control Organization (ECO) in AS 1851-2012?",
"output": "The Emergency Control Organization (ECO) is responsible for implementing the emergency plan in the event of an emergency."
},
{
"instruction": "What are the requirements for emergency evacuation procedures in AS 1851-2012?",
"output": "Emergency evacuation procedures shall be inspected, tested and maintained in accordance with Section 14 of this Standard."
},
{
"instruction": "How often should emergency evacuation procedures be inspected and tested?",
"output": "Emergency evacuation procedures should be inspected and tested six-monthly and yearly."
},
{
"instruction": "What are the requirements for fire-resistant doorsets serving as entry doors to private residential apartments?",
"output": "Fire-resistant doorsets serving as entry doors to private residential apartments may be extended to a yearly service schedule."
},
{
"instruction": "What are the requirements for a system lock-off valve for gaseous fire extinguishing systems?",
"output": "It is recommended that lock-off valves be retrofitted to gaseous fire extinguishing systems, which may result in unsafe concentrations of extinguishing agent developing in occupiable areas."
},
{
"instruction": "What are the requirements for fire dampers in AS 1851-2012?",
"output": "Fire dampers, including intumescent fire dampers, shall be inspected and subjected to a routine service on a yearly basis in accordance with Clause 13.4.1.4."
},
{
"instruction": "How often should fire dampers be inspected and tested?",
"output": "Fire dampers should be inspected and tested yearly."
},
{
"instruction": "What are the requirements for smoke dampers in AS 1851-2012?",
"output": "Smoke dampers shall be inspected and subjected to a routine service on a yearly basis in accordance with Clause 13.4.1.4."
},
{
"instruction": "How often should smoke dampers be inspected and tested?",
"output": "Smoke dampers should be inspected and tested yearly."
},
{
"instruction": "What is the purpose of a pressure gauge schedule for sprinkler systems?",
"output": "A pressure gauge schedule for sprinkler systems is a permanent chart that is water-resistant and fade-resistant, and should include the minimum and maximum standing installation pressure for each installation, minimum and maximum standing below-stop-valve pressure(s), minimum and maximum standing primary and secondary water supply pressure, minimum and maximum standing air pressure, air compressor cut-in and cut-out pressures, low air pressure alarm setting, pump cut-in and shut-off pressure(s), pump pressure-reducing-valve operating pressure, trunk main pressure maintenance pump cut-in and cut-out pressures, installation pressure maintenance pump cut-in and cut-out pressures, installation air pressure, and installation pressure-reducing valve upstream and downstream pressures and relief valve operating pressure."
},
{
"instruction": "What are the requirements for fire-resistant doorsets serving as entry doors to private residential apartments?",
"output": "Fire-resistant doorsets serving as entry doors to private residential apartments may be extended to a yearly service schedule."
},
{
"instruction": "What are the requirements for a system lock-off valve for gaseous fire extinguishing systems?",
"output": "It is recommended that lock-off valves be retrofitted to gaseous fire extinguishing systems, which may result in unsafe concentrations of extinguishing agent developing in occupiable areas."
},
{
"instruction": "What are the requirements for fire dampers in AS 1851-2012?",
"output": "Fire dampers, including intumescent fire dampers, shall be inspected and subjected to a routine service on a yearly basis in accordance with Clause 13.4.1.4."
},
{
"instruction": "How often should fire dampers be inspected and tested?",
"output": "Fire dampers should be inspected and tested yearly."
},
{
"instruction": "What are the requirements for smoke dampers in AS 1851-2012?",
"output": "Smoke dampers shall be inspected and subjected to a routine service on a yearly basis in accordance with Clause 13.4.1.4."
},
{
"instruction": "How often should smoke dampers be inspected and tested?",
"output": "Smoke dampers should be inspected and tested yearly."
},
{
"instruction": "What is the purpose of a pressure gauge schedule for sprinkler systems?",
"output": "A pressure gauge schedule for sprinkler systems is a permanent chart that is water-resistant and fade-resistant, and should include the minimum and maximum standing installation pressure for each installation, minimum and maximum standing below-stop-valve pressure(s), minimum and maximum standing primary and secondary water supply pressure, minimum and maximum standing air pressure, air compressor cut-in and cut-out pressures, low air pressure alarm setting, pump cut-in and shut-off pressure(s), pump pressure-reducing-valve operating pressure, trunk main pressure maintenance pump cut-in and cut-out pressures, installation pressure maintenance pump cut-in and cut-out pressures, installation air pressure, and installation pressure-reducing valve upstream and downstream pressures and relief valve operating pressure."
},
{
"instruction": "What are the requirements for fire-resistant doorsets serving as entry doors to private residential apartments?",
"output": "Fire-resistant doorsets serving as entry doors to private residential apartments may be extended to a yearly service schedule."
},
{
"instruction": "What are the requirements for a system lock-off valve for gaseous fire extinguishing systems?",
"output": "It is recommended that lock-off valves be retrofitted to gaseous fire extinguishing systems, which may result in unsafe concentrations of extinguishing agent developing in occupiable areas."
},
{
"instruction": "What are the requirements for fire dampers in AS 1851-2012?",
"output": "Fire dampers, including intumescent fire dampers, shall be inspected and subjected to a routine service on a yearly basis in accordance with Clause 13.4.1.4."
},
{
"instruction": "How often should fire dampers be inspected and tested?",
"output": "Fire dampers should be inspected and tested yearly."
},
{
"instruction": "What are the requirements for smoke dampers in AS 1851-2012?",
"output": "Smoke dampers shall be inspected and subjected to a routine service on a yearly basis in accordance with Clause 13.4.1.4."
},
{
"instruction": "How often should smoke dampers be inspected and tested?",
"output": "Smoke dampers should be inspected and tested yearly."
},
{
"instruction": "What is the purpose of a pressure gauge schedule for sprinkler systems?",
"output": "A pressure gauge schedule for sprinkler systems is a permanent chart that is water-resistant and fade-resistant, and should include the minimum and maximum standing installation pressure for each installation, minimum and maximum standing below-stop-valve pressure(s), minimum and maximum standing primary and secondary water supply pressure, minimum and maximum standing air pressure, air compressor cut-in and cut-out pressures, low air pressure alarm setting, pump cut-in and shut-off pressure(s), pump pressure-reducing-valve operating pressure, trunk main pressure maintenance pump cut-in and cut-out pressures, installation pressure maintenance pump cut-in and cut-out pressures, installation air pressure, and installation pressure-reducing valve upstream and downstream pressures and relief valve operating pressure."
},
{
"instruction": "What are the requirements for fire-resistant doorsets serving as entry doors to private residential apartments?",
"output": "Fire-resistant doorsets serving as entry doors to private residential apartments may be extended to a yearly service schedule."
},
{
"instruction": "What are the requirements for a system lock-off valve for gaseous fire extinguishing systems?",
"output": "It is recommended that lock-off valves be retrofitted to gaseous fire extinguishing systems, which may result in unsafe concentrations of extinguishing agent developing in occupiable areas."
},
{
"instruction": "What are the requirements for fire dampers in AS 1851-2012?",
"output": "Fire dampers, including intumescent fire dampers, shall be inspected and subjected to a routine service on a yearly basis in accordance with Clause 13.4.1.4."
},
{
"instruction": "How often should fire dampers be inspected and tested?",
"output": "Fire dampers should be inspected and tested yearly."
},
{
"instruction": "What are the requirements for smoke dampers in AS 1851-2012?",
"output": "Smoke dampers shall be inspected and subjected to a routine service on a yearly basis in accordance with Clause 13.4.1.4."
},
{
"instruction": "How often should smoke dampers be inspected and tested?",
"output": "Smoke dampers should be inspected and tested yearly."
},
{
"instruction": "What is the purpose of a pressure gauge schedule for sprinkler systems?",
"output": "A pressure gauge schedule for sprinkler systems is a permanent chart that is water-resistant and fade-resistant, and should include the minimum and maximum standing installation pressure for each installation, minimum and maximum standing below-stop-valve pressure(s), minimum and maximum standing primary and secondary water supply pressure, minimum and maximum standing air pressure, air compressor cut-in and cut-out pressures, low air pressure alarm setting, pump cut-in and shut-off pressure(s), pump pressure-reducing-valve operating pressure, trunk main pressure maintenance pump cut-in and cut-out pressures, installation pressure maintenance pump cut-in and cut-out pressures, installation air pressure, and installation pressure-reducing valve upstream and downstream pressures and relief valve operating pressure."
},
{
"instruction": "What are the requirements for fire-resistant doorsets serving as entry doors to private residential apartments?",
"output": "Fire-resistant doorsets serving as entry doors to private residential apartments may be extended to a yearly service schedule."
},
{
"instruction": "What are the requirements for a system lock-off valve for gaseous fire extinguishing systems?",
"output": "It is recommended that lock-off valves be retrofitted to gaseous fire extinguishing systems, which may result in unsafe concentrations of extinguishing agent developing in occupiable areas."
},
{
"instruction": "What are the requirements for fire dampers in AS 1851-2012?",
"output": "Fire dampers, including intumescent fire dampers, shall be inspected and subjected to a routine service on a yearly basis in accordance with Clause 13.4.1.4."
},
{
"instruction": "How often should fire dampers be inspected and tested?",
"output": "Fire dampers should be inspected and tested yearly."
},
{
"instruction": "What are the requirements for smoke dampers in AS 1851-2012?",
"output": "Smoke dampers shall be inspected and subjected to a routine service on a yearly basis in accordance with Clause 13.4.1.4."
},
{
"instruction": "How often should smoke dampers be inspected and tested?",
"output": "Smoke dampers should be inspected and tested yearly."
},
{
"instruction": "What is the purpose of a pressure gauge schedule for sprinkler systems?",
"output": "A pressure gauge schedule for sprinkler systems is a permanent chart that is water-resistant and fade-resistant, and should include the minimum and maximum standing installation pressure for each installation, minimum and maximum standing below-stop-valve pressure(s), minimum and maximum standing primary and secondary water supply pressure, minimum and maximum standing air pressure, air compressor cut-in and cut-out pressures, low air pressure alarm setting, pump cut-in and shut-off pressure(s), pump pressure-reducing-valve operating pressure, trunk main pressure maintenance pump cut-in and cut-out pressures, installation pressure maintenance pump cut-in and cut-out pressures, installation air pressure, and installation pressure-reducing valve upstream and downstream pressures and relief valve operating pressure."
},
{
"instruction": "What are the requirements for fire-resistant doorsets serving as entry doors to private residential apartments?",
"output": "Fire-resistant doorsets serving as entry doors to private residential apartments may be extended to a yearly service schedule."
},
{
"instruction": "What are the requirements for a system lock-off valve for gaseous fire extinguishing systems?",
"output": "It is recommended that lock-off valves be retrofitted to gaseous fire extinguishing systems, which may result in unsafe concentrations of extinguishing agent developing in occupiable areas."
},
{
"instruction": "What are the requirements for fire dampers in AS 1851-2012?",
"output": "Fire dampers, including intumescent fire dampers, shall be inspected and subjected to a routine service on a yearly basis in accordance with Clause 13.4.1.4."
},
{
"instruction": "How often should fire dampers be inspected and tested?",
"output": "Fire dampers should be inspected and tested yearly."
},
{
"instruction": "What are the requirements for smoke dampers in AS 1851-2012?",
"output": "Smoke dampers shall be inspected and subjected to a routine service on a yearly basis in accordance with Clause 13.4.1.4."
},
{
"instruction": "How often should smoke dampers be inspected and tested?",
"output": "Smoke dampers should be inspected and tested yearly."
},
{
"instruction": "What is the purpose of a pressure gauge schedule for sprinkler systems?",
"output": "A pressure gauge schedule for sprinkler systems is a permanent chart that is water-resistant and fade-resistant, and should include the minimum and maximum standing installation pressure for each installation, minimum and maximum standing below-stop-valve pressure(s), minimum and maximum standing primary and secondary water supply pressure, minimum and maximum standing air pressure, air compressor cut-in and cut-pressures"
}
]